Analog Devices ADE7761 Manuals

ManualLib has 2 documents for the Analog Devices ADE7761: 2 datasheets. Every file can be read online or downloaded as a PDF for free.

Datasheet 2

Key facts

Model
ADE7761
Industry
Industrial
Documents
2
Languages
EN
Last added
2012-03-28

Start here

Analog Devices ADE7761 Datasheet

Analog Devices ADE7761 Datasheet

Datasheet 28 pages · 312 KB · EN

The ADE7761 is a high‑accuracy energy‑metering IC designed for 2‑wire distribution systems. It provides active‑energy measurement, fault detection, and missing‑neutral detection, with outputs for average and instantaneous power.

The document includes functional block diagrams, pin descriptions, electrical specifications, timing diagrams, and application notes for interfacing the device to a microcontroller or energy‑metering system.

Read online

Analog Devices ADE7761 specifications

Measurement Error0.1 % of reading (typ)
Phase Error between Channels (PF = 0.8 Capacitive)+0.05° max
Logic Input High Voltage24 V (min)
Logic Output High Voltage4 V (min)
Operating Temperature Range-40 °C to +85 °C
Supply Voltage (Vop)5 V ±5 %
Oscillator Frequency450 kHz
Input Bandwidth (‑3 dB)7 kHz (typ)
ADC Offset Error10 mV (max)

Source: Analog Devices ADE7761 Datasheet

All Analog Devices ADE7761 documents by type

Datasheet 2

Ratings, dimensions and ordering codes, for selection and design work.

Questions answered in these manuals

What is the fault detection threshold for the ADE7761?

The device flags a fault when the phase and neutral currents differ by more than 6.25 %.

From: Analog Devices ADE7761 Datasheet

How does the ADE7761 indicate a missing neutral condition?

A missing neutral condition is indicated when the FAULT pin goes high.

From: Analog Devices ADE7761 Datasheet

What is the measurement error of the ADE7761?

The ADE7761 has a typical measurement error of 0.1 % of reading over a dynamic range of 500 : 1.

From: Analog Devices ADE7761 Datasheet

How does the ADE7761 detect a missing neutral condition?

It continuously monitors the input voltage; when no voltage is present, the FAULT pin goes high to indicate a missing neutral condition.

From: Analog Devices ADE7761 Datasheet