User Manual 8 pages · 163 KB · EN

This manual contains important safety information for the SITOP Smart 24 V power supplies. Only qualified personnel may work on the equipment, the main switch must be turned off and locked out before any installation or maintenance, and a protective device (fuse) and disconnecting device must be provided. The units must be mounted vertically with a minimum 50 mm clearance above and below, and the input and output terminals must face downward.

The document also lists the electrical characteristics of the supplies: input voltage 120/230 V AC, input voltage range 85‑132 V / 170‑264 V AC, frequency 47‑63 Hz, output voltage 24 V DC, ripple <150/240 mV, efficiency up to 91 % at full load, protection class I, IP 20, operating temperature 0 °C‑+60 °C and storage temperature –40 °C‑+85 °C. Parallel operation of two identical units is allowed under specific conditions.

Read online

Siemens 6EP1333-2AA01 specifications

Input nominal voltage120/230 V AC
Input voltage range85‑132 V / 170‑264 V AC
Input frequency range47‑63 Hz
Output nominal voltage24 V DC
Output ripple / spikes< 150/240 mV
Protection classI
IP ratingIP 20
Operating temperature range0 °C … +60 °C
Storage temperature range-40 °C … +85 °C

Source: SIEMENS 6EP1332-2BA10 6EP1333-2BA01 6EP1334-2BA01 6EP1334-2AA01-0AA0 6EP1333-2AA01 6EP1334-2AA01 handbook

All Siemens 6EP1333-2AA01 documents by type

Questions answered in these manuals

What safety steps must be taken before installing or servicing the SITOP power supply?

The main switch must be turned off and locked out, only qualified personnel may work on the equipment, and a protective device (fuse) and a disconnecting device must be provided.

From: SIEMENS 6EP1332-2BA10 6EP1333-2BA01 6EP1334-2BA01 6EP1334-2AA01-0AA0 6EP1333-2AA01 6EP1334-2AA01 handbook

How should the SITOP unit be mounted for proper cooling?

The device must be installed vertically with the input and output terminals at the bottom and a minimum free space of 50 mm above and below the unit.

From: SIEMENS 6EP1332-2BA10 6EP1333-2BA01 6EP1334-2BA01 6EP1334-2AA01-0AA0 6EP1333-2AA01 6EP1334-2AA01 handbook

What safety precautions must be taken before installing the SITOP Smart power supply?

Only qualified personnel should install or service the unit, power must be disconnected, and DIN 7437, IEC60364, and EN 50178 guidelines must be followed.

From: SIEMENS SITOP Smart 2 5 6EP1332-2BA10 SITOP Smart 5 6EP1333-2AA01 6EP1333-2BA01 SITOP Smart 10 6EP1334-2AA01 6EP1334-2BA01 operating Manual

What is the required input voltage for the SITOP Smart series?

The power supplies accept an AC input voltage of 120 V to 230 V at 50 Hz or 60 Hz.

From: SIEMENS SITOP Smart 2 5 6EP1332-2BA10 SITOP Smart 5 6EP1333-2AA01 6EP1333-2BA01 SITOP Smart 10 6EP1334-2AA01 6EP1334-2BA01 operating Manual