OMRON E5CN/E5CN-U Manuals

ManualLib has 6 documents for the OMRON E5CN/E5CN-U (Other Electronics): 1 product leaflet, 1 datasheet, 3 user manuals. Every file can be read online or downloaded as a PDF for free.

Product Leaflet 1Datasheet 1User Manual 3

Key facts

Brand
Omron
Model
E5CN/E5CN-U
Industry
Industrial
Documents
6
Languages
EN · ES · ZH
Last added
2026-11-10

Start here

Omron E5CN/E5CN-U Digital Thermostat User Manual

Omron E5CN/E5CN-U Digital Thermostat User Manual

User Manual 18 pages · 2 MB · ZH

This manual describes the Omron E5CN/E5CN-U digital thermostat family, including the basic model and the U‑type (plug‑in) version. It covers product selection, input/output functions, control output configurations, and safety notes for installation and maintenance.

The document also includes technical data such as indicator accuracy, power‑supply ranges, waterproof ratings, and wiring diagrams for various control output options (1‑point, 2‑point, AC 100‑240 V, AC/DC 24 V). Reference tables list model codes, terminal configurations, and optional accessories like adapters and terminal blocks. This manual is written in Chinese.

Read online

OMRON E5CN/E5CN-U specifications

Display Type2 line display: PV and SV 4-digit, 11 segment display
Indication Accuracy (Thermocouple)±0.3% of PV
Indication Accuracy (Pt)±0.2% of PV
Indication Accuracy (Analog)±0.2% FS
Sampling Period250 ms
Control MethodON/OFF control or 2-PID control (with auto-tuning)
Power Supply Voltage (No D)100 to 240 VAC, 50/60 Hz
Power Supply Voltage (D)24 VAC, 50/60 Hz; 24 VDC
Operating Temperature-10 to 55 °C
Operating Humidity25% to 85%

Source: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet

All OMRON E5CN/E5CN-U documents by type

Datasheet 1

Ratings, dimensions and ordering codes, for selection and design work.

User Manual 3

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What is the indication accuracy for thermocouple inputs?

The indication accuracy for thermocouple inputs is ±0.3% of PV.

From: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet

What control methods are supported?

The controller supports ON/OFF control or 2-PID control with auto-tuning.

From: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet

What is the sampling period of the E5CN controller?

The controller samples at a period of 250 ms.

From: Omron E5CN/E5CN-U Temperature Controller Datasheet

What output types are available for the E5CN series?

The series offers relay (R), voltage for SSR (Q), current (C) and long‑life relay (Y) outputs.

From: Omron E5CN/E5CN-U Temperature Controller Datasheet

What input types are supported by the E5CN/E5CN-U controllers?

They accept universal thermocouple or platinum‑resistance thermometer inputs and, for analog models, current (4‑20 mA) or voltage (0‑10 V) inputs.

From: Omron E5CN/E5CN-U Basic-type Digital Temperature Controller Handbook

How many auxiliary outputs can the controller have?

Depending on the model, the controller can have up to two auxiliary outputs.

From: Omron E5CN/E5CN-U Basic-type Digital Temperature Controller Handbook