Key facts
- Brand
- Omron
- Model
- E5CN/E5CN-U
- Category
- Other Electronics
- Industry
- Industrial
- Documents
- 6
- Languages
- EN · ES · ZH
- Last added
- 2026-11-10
Start here

Omron E5CN/E5CN-U Digital Thermostat User Manual
This manual describes the Omron E5CN/E5CN-U digital thermostat family, including the basic model and the U‑type (plug‑in) version. It covers product selection, input/output functions, control output configurations, and safety notes for installation and maintenance.
The document also includes technical data such as indicator accuracy, power‑supply ranges, waterproof ratings, and wiring diagrams for various control output options (1‑point, 2‑point, AC 100‑240 V, AC/DC 24 V). Reference tables list model codes, terminal configurations, and optional accessories like adapters and terminal blocks. This manual is written in Chinese.
OMRON E5CN/E5CN-U specifications
| Display Type | 2 line display: PV and SV 4-digit, 11 segment display |
|---|---|
| Indication Accuracy (Thermocouple) | ±0.3% of PV |
| Indication Accuracy (Pt) | ±0.2% of PV |
| Indication Accuracy (Analog) | ±0.2% FS |
| Sampling Period | 250 ms |
| Control Method | ON/OFF control or 2-PID control (with auto-tuning) |
| Power Supply Voltage (No D) | 100 to 240 VAC, 50/60 Hz |
| Power Supply Voltage (D) | 24 VAC, 50/60 Hz; 24 VDC |
| Operating Temperature | -10 to 55 °C |
| Operating Humidity | 25% to 85% |
Source: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet
All OMRON E5CN/E5CN-U documents by type
Ratings, dimensions and ordering codes, for selection and design work.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the indication accuracy for thermocouple inputs?
The indication accuracy for thermocouple inputs is ±0.3% of PV.
From: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet
What control methods are supported?
The controller supports ON/OFF control or 2-PID control with auto-tuning.
From: OMRON E5CN/E5CN-U Basic-type Digital Temperature Controller Data Sheet
What is the sampling period of the E5CN controller?
The controller samples at a period of 250 ms.
What output types are available for the E5CN series?
The series offers relay (R), voltage for SSR (Q), current (C) and long‑life relay (Y) outputs.
What input types are supported by the E5CN/E5CN-U controllers?
They accept universal thermocouple or platinum‑resistance thermometer inputs and, for analog models, current (4‑20 mA) or voltage (0‑10 V) inputs.
From: Omron E5CN/E5CN-U Basic-type Digital Temperature Controller Handbook
How many auxiliary outputs can the controller have?
Depending on the model, the controller can have up to two auxiliary outputs.
From: Omron E5CN/E5CN-U Basic-type Digital Temperature Controller Handbook