Start here

SYSMAC CS1W-CLK23 CS1W-CLK21-V1 CJ1W-CLK23 CJ1W-CLK21-V1 C200HW-CLK21 CVM1-CLK21 CQM1H-CLK21 (CS1W-RPT01/02/03 Repeater Units) Controller Link Units Operation Manual
This manual provides operating instructions for OMRON CS/CJ-series Controller Link Units, including models CS1W-CLK23, CS1W-CLK21-V1, CJ1W-CLK23, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, and CQM1H-CLK21. It details system configurations, unit versions, and basic procedures for establishing data links between Programmable Controllers (PLCs) and IBM PC/AT compatible computers.
Read onlineOMRON CS1W-CLK21-V1 specifications
| Maximum data link words (unit version 2.0) | 20,000 max. |
|---|---|
| Send words per node (manually set data links) | 4,000 words max. |
| Send words per node (unit version 1.2) | 1,000 words max. |
| Controller Link Units connected to one CPU Unit | 8 Units (unit version 2.0) or 4 Units (earlier versions) |
All OMRON CS1W-CLK21-V1 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
- SYSMAC CS1W-CLK23 CS1W-CLK21-V1 CJ1W-CLK23 CJ1W-CLK21-V1 C200HW-CLK21 CVM1-CLK21 CQM1H-CLK21 (CS1W-RPT01/02/03 Repeater Units) Controller Link Units Operation Manual 400 p
- OMRON Controller Link Units Operation Manual 401 p
- SYSMAC CS1W-CLK23 CS1W-CLK21-V1 CJ1W-CLK23 CJ1W-CLK21-V1 C200HW-CLK21 CVM1-CLK21 CQM1H-CLK21 (CS1W-RPT01/02/03 Repeater Units) Controller Link Units Operation Manual 402 p
- OMRON SYSMAC CS1W-CLK21-V1 CJ1W-CLK21-V1 C200HW-CLK21 CVM1-CLK21 CQM1H-CLK21 (CS1W-RPT01/02/03 Repeater Units)Controller Link Units Manual 383 p
Questions answered in these manuals
How can the unit version be confirmed with support software?
CX-Programmer version 5.0 or higher can be used to confirm the unit version in the Unit Manufacturing information.
What software version is needed to set data link tables with more than 1,000 send words per node?
Use the CX-Integrator Data Link Setting Tool version 3.2.1.1 or later.
Can the same data link area be allocated for both Area 1 and Area 2?
Yes, the same area can be allocated for both Area 1 and Area 2 in Unit version 1.2 or later.
Which repeater units are required when using optical fiber?
Two Repeater Units of the same model, specifically CS1W-RPT02 or CS1W-RPT03, must be used when part of the transmission line uses optical fiber.
What is the maximum number of Controller Link Units that can be connected to a single CPU Unit?
The maximum number of Units connected to a single CPU Unit is 8 Units.
Which software is required to confirm the unit version of a Controller Link Unit?
CX-Programmer version 5.0 or higher can be used to confirm the unit version in the Unit Manufacturing Information.