SYSMAC CS1W-CLK23 CS1W-CLK21-V1 CJ1W-CLK23 CJ1W-CLK21-V1 C200HW-CLK21 CVM1-CLK21 CQM1H-CLK21 (CS1W-RPT01/02/03 Repeater Units) Controller Link Units Operation Manual
This manual provides operating instructions for OMRON CS/CJ-series Controller Link Units, including models CS1W-CLK23, CS1W-CLK21-V1, CJ1W-CLK23, CJ1W-CLK21-V1, C200HW-CLK21, CVM1-CLK21, and CQM1H-CLK21. It details system configurations, unit versions, and basic procedures for establishing data links between Programmable Controllers (PLCs) and IBM PC/AT compatible computers.
Read onlineOMRON CS1W-CLK23 specifications
| Maximum number of data link words | 20,000 max. (Unit version 2.0) |
|---|---|
| Number of send words per node | 4,000 words max. (Unit version 2.0) |
| Maximum number of Units connected | 8 Units (Unit version 2.0) |
All OMRON CS1W-CLK23 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
Can the same data link area be allocated for both Area 1 and Area 2?
Yes, the same area can be allocated for both Area 1 and Area 2 in Unit version 1.2 or later.
Which repeater units are required when using optical fiber?
Two Repeater Units of the same model, specifically CS1W-RPT02 or CS1W-RPT03, must be used when part of the transmission line uses optical fiber.
What is the maximum number of Controller Link Units that can be connected to a single CPU Unit?
The maximum number of Units connected to a single CPU Unit is 8 Units.
Which software is required to confirm the unit version of a Controller Link Unit?
CX-Programmer version 5.0 or higher can be used to confirm the unit version in the Unit Manufacturing Information.