ABB ACQ580 Drives for Water User Manual
ABB ACQ580 Drives for Water is a pump control drive. This document is its French user manual and covers startup, I/O control, motor identification, microconsole operation, settings, diagnostics, functions, fault location, fieldbus networking, control logic diagrams, and parameter descriptions.
The manual is document 3AXD50000044881 Rev G, dated 14/03/2023, and is a translation of document 3AXD50000035867 Rev G. Its table of contents lists sections from getting started through additional parameter information. This manual is written in French.
ABB ACQ580 specifications
| THDi (harmonic distortion) with ULH drive | ≈ 3 % |
|---|---|
| System efficiency with ULH drive (typical load) | ≈ 87.9 % |
| Harmonic content under rated load | 3 % |
| Power factor improvement | approaches 1.0 |
Source: ABB ACS880/ACH580/ACQ580 Low Harmonic and Energy Feedback Inverter Application Note
All ABB ACQ580 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Mounting, wiring and first power-up. Read it before the hardware goes in.
How to use the product for one specific task, with worked examples.
Questions answered in these manuals
What product does this manual cover?
ABB DRIVES FOR WATER ACQ580 pump control drive.
What is the document number and revision?
3AXD50000044881 Rev G.
What must be done if the drive has not been powered for a year or more?
The DC link capacitors must be reformed. Refer to the related manuals list or contact ABB technical support.
From: ABB ACQ580-04 Water Application Drive Quick Installation Guide
What motor cable does ABB recommend?
ABB recommends using symmetric shielded VFD motor cable.
From: ABB ACQ580-04 Water Application Drive Quick Installation Guide
What voltage is required to measure insulation resistance between each phase wire and the PE conductor?
You must use a measurement voltage of 1000VDC.
From: ABB ACQ580-01 VFD Quick Installation and Startup Guide
What torque value should be used when tightening the cable clamp for power cables?
Tighten the cable clamp with a torque of 1.2 N-m (10.6 lbf-in).
From: ABB ACQ580-01 VFD Quick Installation and Startup Guide