Key facts
- Brand
- ABB
- Model
- ACS800-17
- Industry
- Industrial
- Documents
- 5
- Languages
- ZH · EN
- Last added
- 2026-10-26
Start here

ABB ACS800-17 Quadrant Cabinet Drive Hardware Manual
The document is a hardware manual for the ABB ACS800-17 four-quadrant cabinet drive with power ratings from 55 to 2500 kW. It serves as a comprehensive guide for qualified personnel involved in the installation, debugging, operation, and maintenance of the drive unit. This manual is written in Chinese.
Read onlineABB ACS800-17 specifications
| Analogue input resolution | 0.025 % (12 bit) |
|---|---|
| Digital input logical thresholds | < 8 VDC “0”, > 12 VDC “1” |
| Relay output switching capacity | 8 A at 24 VDC or 250 VAC |
| Rated apparent supply power | 260 kVA to 4728 kVA |
All ABB ACS800-17 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Disassembly, diagnostics and part numbers, for repair.
Questions answered in these manuals
Who is qualified to install and maintain the drive unit?
Only qualified electrical engineers can install and maintain the drive unit.
How long must one wait after cutting power before maintenance?
One must wait at least 5 minutes to allow the intermediate DC circuit capacitors to discharge.
Who is allowed to install and maintain the ACS800‑17 drive?
Only qualified electrical engineers may install and maintain the drive unit.
How can I verify that the drive is fully discharged before starting work?
After cutting power, wait at least five minutes, then measure the resistance between UDC+ and UDC‑ (L+ and L‑); it must be at least 1 MΩ to confirm discharge.
What safety precautions must be taken before working on the drive?
The drive must be isolated from the supply, the input power turned off, and a 5‑minute wait is required before starting work. Verify discharge by measuring voltage between UDC+ and UDC‑, and apply temporary grounding.
How should the drive be grounded?
The drive, motor, and adjoining equipment must be connected to a protective earth conductor sized according to safety regulations, with a minimum cross‑section of 10 mm² Cu or 16 mm² Al.