Mitsubishi FR-F500-CH Series Speed Governor Manual
The FR‑F500‑CH series speed governor provides pre‑set PID control for up to four motors used in pumps or fans. The document describes how to configure motor count, switching mode, and PID parameters using the Pr.500‑Pr.501 settings.
System composition, wiring diagrams, and detailed parameter tables are included, covering auxiliary motor start/stop frequencies, delay times, MC interlock settings, and output‑interrupt detection. The manual also lists required external equipment and safety considerations for proper installation and operation. This manual is written in Chinese.
Mitsubishi FR-F500-CH specifications
| Auxiliary Motor 1 Start Frequency Range | 0–120 Hz (step 0.01 Hz, default 50 Hz) |
|---|---|
| Auxiliary Motor 1 Stop Frequency Range | 0–120 Hz (step 0.01 Hz, default 0 Hz) |
| Auxiliary Motor Start Delay Time | 0–3600 s (step 0.1 s, default 5 s) |
| Auxiliary Motor Stop Delay Time | 0–3600 s (step 0.1 s, default 5 s) |
| Output Interruption Detection Time | 0–3600 s (step 0.1 s, default 9999 s disables) |
Source: Henan Quanshen FR-F500-CH Soft Starter PID Control Supplement Manual
All Mitsubishi FR-F500-CH documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
How many motors can be controlled with the PID function?
The PID control function can operate up to four motors.
From: Henan Quanshen FR-F500-CH Soft Starter PID Control Supplement Manual
Which parameter selects the motor switching mode?
Parameter Pr.501 “电机切换选择” selects the motor switching mode.
From: Henan Quanshen FR-F500-CH Soft Starter PID Control Supplement Manual
How do I select the motor switching method?
Set parameter Pr.501 "电机切换选择" to 0 for basic, 1 for alternating, or 2 for direct mode.
Which signal controls the PID action direction?
Assign the X24 signal to any of Pr.180‑Pr.186; X24 ON selects positive action, X24 OFF selects reverse action.