Mitsubishi FR-F500-CH Series Speed Governor Manual

This manual introduces the pre-PID control function of the FR-F500-CH series inverter, including function overview, system structure, parameter setting and other contents.


Brand
Mitsubishi
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
194
File format
PDF
File size
5 MB
Updated
01 October, 2023
MD5 checksum
B5D7FC511023DF8485197E37DB6E6B11

About this manual

The FR‑F500‑CH series speed governor provides pre‑set PID control for up to four motors used in pumps or fans. The document describes how to configure motor count, switching mode, and PID parameters using the Pr.500‑Pr.501 settings.

System composition, wiring diagrams, and detailed parameter tables are included, covering auxiliary motor start/stop frequencies, delay times, MC interlock settings, and output‑interrupt detection. The manual also lists required external equipment and safety considerations for proper installation and operation. This manual is written in Chinese.

What's inside

  • 系统构成
  • 电机切换时机
  • PID控制
  • 输出中断检测
  • 基本配置
  • 参数设定
  • 附录 数据代码

Specifications

Auxiliary Motor 1 Start Frequency0–120 Hz (default 50 Hz)
Auxiliary Motor 1 Stop Frequency0–120 Hz (default 0 Hz)
Auxiliary Motor Start Delay (Pr.515)0–3600 s, step 0.1 s (default 5 s)
Auxiliary Motor Stop Delay (Pr.516)0–3600 s, step 0.1 s (default 5 s)
MC Interlock Switch Time (Pr.502)0–100 s, step 0.1 s (default 1 s)
Startup Waiting Time (Pr.503)0–100 s, step 0.1 s (default 1 s)

Frequently asked questions

How do I select the motor switching method?

Set parameter Pr.501 "电机切换选择" to 0 for basic, 1 for alternating, or 2 for direct mode.

Which signal controls the PID action direction?

Assign the X24 signal to any of Pr.180‑Pr.186; X24 ON selects positive action, X24 OFF selects reverse action.

How can I set the start delay for an auxiliary motor?

Adjust parameter 515 "辅助电机启动延迟时间" to the desired number of seconds.

What is the default start frequency for auxiliary motor 1?

The factory default start frequency is 50 Hz.

Download PDF (5 MB)