Key facts
- Brand
- Honeywell
- Model
- HEL-700
- Industry
- Industrial
- Documents
- 2
- Languages
- EN · ZH
- Last added
- 2012-05-07
Start here

Honeywell HEL-700 Platinum RTD Handbook
The HEL-700 series are thin‑film platinum resistance temperature detectors offering linear resistance versus temperature, high accuracy, and excellent stability. They are available in 1000 V and 100 V versions with multiple packaging options such as ribbon lead, radial chip, and SMT axial.
The document lists detailed specifications including temperature range, accuracy, time constants, and recommended operating currents, as well as ordering guides for various lead‑wire configurations and optional NIST calibrations.
Honeywell HEL-700 specifications
| Sensor Type | Thin film platinum RTD |
|---|---|
| Base Resistance (1000 V) | 1000 V @ 0 °C |
| Alpha (1000 V) | 0.00375 V/V/°C |
| Temperature Range (Teflon leads) | -200 °C to +260 °C |
| Temperature Accuracy (standard) | ±0.5 °C or 0.8 % of temperature |
| Time Constant (water) | <0.5 s |
| Operating Current | 2 mA max (1 mA recommended) |
| Insulation Resistance | >50 MΩ at 50 VDC @ 25 °C |
| Lead Material | Nickel‑coated stranded copper, Teflon or Fiberglass insulated |
All Honeywell HEL-700 documents by type
Ratings, dimensions and ordering codes, for selection and design work.
Questions answered in these manuals
What temperature range does the HEL-700 RTD support with Teflon leads?
The HEL-700 RTD with Teflon leads operates from –200 °C to +260 °C.
What is the typical accuracy of the standard HEL-700 RTD?
The standard HEL-700 RTD provides a temperature accuracy of ±0.5 °C or 0.8 % of temperature.
What is the temperature range of the Honeywell HEL-700 sensor?
It operates from -200°C to 540°C in chip or strip-lead packages.
What resistance tolerance options are available for the HEL-700?
Standard tolerance is ±0.2% and optional tolerance is ±0.1%.