Honeywell HEL-775-A/B Temperature Sensor Datasheet

Honeywell HEL-775-A/B Temperature Sensor Datasheet

Datasheet 1 pages · 48 KB · ZH

The HEL-775 series are thin‑film platinum RTD (RTD) temperature sensors offered in two variants, A and B. They feature interchangeable resistance values, high accuracy, linear response, fast response time, laser‑trimmed correction, solder‑able SIP packaging, and a ceramic substrate.

Performance specifications include a temperature range of -55 °C to 150 °C, accuracy better than ±0.5 °C (0.8 % of reading) for the A version and ±0.3 °C (0.6 % of reading) for the B version, resistance of 1000 Ω (A) or 100 Ω (B) at 0 °C with tight tolerance, low self‑heat (<0.3 °C), and high insulation resistance (>50 MΩ at 25 °C). The sensors are supplied in a solderable SIP package with 0.100 in lead spacing. This manual is written in Chinese.

Read online

Honeywell HEL-775 specifications

Sensor typeThin‑film platinum RTD
Temperature range-55 °C to 150 °C
Accuracy (HEL-775-A)±0.5 °C or 0.8 % of reading
Accuracy (HEL-775-B)±0.3 °C or 0.6 % of reading
Resistance at 0 °C (HEL-775-A)1000 Ω ± 2 Ω (±0.2 %)
Resistance at 0 °C (HEL-775-B)100 Ω ± 0.2 Ω (±0.2 %)
Alpha coefficient (HEL-775-A)0.00375 Ω/Ω/°C
Alpha coefficient (HEL-775-B)0.00385 Ω/Ω/°C
Power dissipation (10 ft/s air)9.7 mW/°C
Insulation resistance>50 MΩ @ 25 °C
PackageSolderable SIP, 0.100 in lead spacing

Source: Honeywell HEL-775-A/B Temperature Sensor Datasheet

All Honeywell HEL-775 documents by type

Questions answered in these manuals

What is the temperature measurement range of the HEL-775 sensors?

The HEL-775 sensors operate from -55 °C up to 150 °C.

From: Honeywell HEL-775-A/B Temperature Sensor Datasheet

What is the accuracy of the HEL-775-A sensor?

The HEL-775-A provides accuracy better than ±0.5 °C or 0.8 % of the reading (laser‑trimmed ±0.2 %).

From: Honeywell HEL-775-A/B Temperature Sensor Datasheet

What temperature range does the HEL-775 sensor cover?

It measures temperatures from –55 °C up to 150 °C.

From: Honeywell HEL-775 Temperature Sensor Datasheet

What is the accuracy of the HEL-775 temperature sensor?

The sensor’s accuracy is better than ±0.5 °C or 0.8 % of the current temperature reading.

From: Honeywell HEL-775 Temperature Sensor Datasheet

What temperature range does the HEL-775 sensor cover?

The HEL-775 operates from –55 °C up to 150 °C.

From: Honeywell HEL-775 Temperature Sensor Datasheet

What is the accuracy of the HEL-775 temperature sensor?

Its accuracy is better than ±0.5 °C or 0.8 % of the reading, whichever is larger.