Start here

Hitachi WL200 Series Inverter Basic Manual
The Hitachi WL200 Series Inverter Basic Manual covers essential safety and operational information for the WL200 series inverters, which accept single-phase 200V and three-phase 400V input. It is intended for end users and must be read before installing or operating the inverter.
The manual details safety precautions for installation, wiring, operation, and maintenance, including UL compliance markings and terminal specifications such as screw sizes, tightening torques, and wire ranges for each model variant.
Hitachi WL200 series specifications
| Maximum surrounding air temperature | 50 °C |
|---|---|
| Motor overload protection | 150% of FLA |
| Short-circuit current rating | 100,000 rms symmetrical amperes at 240 or 480 V |
| Wire temperature rating (for some models) | 60/75 °C copper wire only |
All Hitachi WL200 series documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Mounting, wiring and first power-up. Read it before the hardware goes in.
Questions answered in these manuals
What is the maximum surrounding air temperature rating for the WL200 inverter?
The maximum surrounding air temperature rating is 50 °C.
What wire temperature rating is required for models like WL200-022S?
Models such as WL200-022S require 60/75 °C copper wire only.
What EMC standard does this guide follow?
The guide follows EN 61800-3 for emissions and immunity standards.
What is the maximum recommended length for the motor cable?
The motor cable length should not exceed 50m to avoid increased capacitive current and electromagnetic emission.