Start here

Hitachi WJ200 Inverter Quick Reference Guide
This guide provides essential safety instructions and operational procedures for installing, wiring, and maintaining the Hitachi WJ200 inverter. It includes warnings for electrical hazards, installation requirements, and maintenance precautions. The guide also covers operating modes, emergency stop procedures, and safe handling practices to prevent injury or equipment damage.
The document is intended for end users and includes specific safety classifications (PELIGRO and PRECAUCIÓN) to highlight critical risks. It emphasizes proper grounding, qualified electrical work, and adherence to manufacturer specifications to ensure safe operation and prevent fire or injury. This manual is written in Spanish.
Hitachi WJ200 specifications
| Rated input voltage (single‑phase) | 200 V‑15% to 240 V +10% |
|---|---|
| Rated output voltage (three‑phase) | 200 V to 240 V (proportional to input) |
| Rated capacity (kVA) for VT 0.4 model | 0.4 kVA |
| Maximum surrounding air temperature | 50 °C |
All Hitachi WJ200 documents by type
The shortest path to a working setup, usually only a few pages.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Disassembly, diagnostics and part numbers, for repair.
Questions answered in these manuals
What is the maximum recommended motor cable length for Hitachi WJ200 inverters?
The motor cable length should not exceed 50m to avoid electromagnetic emission and capacitive currents.
What safety precautions should be taken when installing the line filter?
Wait at least 60 seconds after switching off the line voltage before touching terminals or removing protective covers to avoid electric shock.
What voltage classes are supported for single-phase and three-phase inputs?
The inverter supports a single-phase input of class 200 V and three-phase inputs of class 200 V or 400 V.
What is the minimum waiting time required before inspecting the inverter after disconnecting power?
You must wait at least 10 minutes before inspecting the inverter after disconnecting the power supply.
What type of wire is recommended for the WJ200 series?
The manual recommends using 60/75°C Cu wire or equivalent for specific models.
What is the minimum wait time required after turning off the input power before performing maintenance?
You must wait at least five minutes after turning off the input power supply before performing maintenance or an inspection.