User Manual 19 pages · 672 KB · ZH

The Delta DVP04AD-SL is an open-type analog input module designed for use with DVP series PLCs. It features four input channels that can be configured to read either voltage or current signals. The module converts 16-bit digital data from the PLC MPU into analog input signals, supporting ranges such as ±10VDC for voltage and ±20mA to 20mA for current. This manual is written in Chinese.

Read online

Delta DVP-04AD-S specifications

Input TypeVoltage or Current
Current Input Range±20mA
Resolution14-bit (1 LSB=1.25 mV) for voltage, 13-bit (1 LSB=5 µA) for current
Power Supply24VDC (20.4VDC~28.8VDC)
Response Time3 ms per channel

Source: Delta DVP-04AD-S Analog Input Module User Manual

All Delta DVP-04AD-S documents by type

User Manual 2

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Installation Guide 1

Mounting, wiring and first power-up. Read it before the hardware goes in.

Questions answered in these manuals

How many channels does the DVP-04AD-S module have?

It has 4 analog input channels.

From: Delta DVP-04AD-S Analog Input Module User Manual

What is the maximum power consumption of the module?

The maximum power consumption is 2W with external power supply.

From: Delta DVP-04AD-S Analog Input Module User Manual

What is the voltage input range for Mode 0?

Mode 0 supports a voltage input range of ±10V.

From: Delta DVP04AD-SL Analog Input Module User Manual

How do you configure the input mode for Channel 1?

You set the input mode using Control Register CR#2.

From: Delta DVP04AD-SL Analog Input Module User Manual

What torque should be applied to the I/O terminal block screws?

The tightening torque for the I/O terminal block is 1.95 kg‑cm (1.7 in‑lbs).

From: Delta DVP-04AD-SL Installation Manual

What safety step must be taken before wiring the module?

Disconnect the input AC power supply and verify all wiring before powering the module; do not touch internal wiring within one minute after power is removed.

From: Delta DVP-04AD-SL Installation Manual