Key facts
- Brand
- Delta
- Model
- DVPPS02
- Category
- Power Management
- Industry
- Industrial
- Documents
- 2
- Languages
- JA · ZH
- Last added
- 2012-01-17
Start here

Delta DVPPS01 DVPPS02 Power Module User Manual
The DVPPS01 and DVPPS02 are 24 VDC output power modules designed for use with Delta DVP series PLCs. They offer compact size, easy installation and separate power supply from the main controller.
The manual covers safety precautions, wiring instructions, mounting methods, environmental limits, and troubleshooting. It also lists the electrical specifications such as input voltage range, output voltage and current, and operating temperature. This manual is written in Japanese.
Delta DVPPS02 specifications
| Input voltage range | 100~240 VAC, 50/60 Hz |
|---|---|
| Output voltage (DVPPS01/DVPPS02) | 24 VDC (±3%) |
| Maximum output current (DVPPS01) | 1 A |
| Maximum output current (DVPPS02) | 2 A |
| Ripple & noise (DVPPS01) | < 100 mV p‑p at full load |
| Ripple & noise (DVPPS02) | < 240 mV p‑p at full load |
| Efficiency (full load) | 78%–87% |
| Operating temperature | 0 °C to 55 °C |
| Storage temperature | -25 °C to 70 °C |
All Delta DVPPS02 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What input voltage range does the DVPPS01/DVPPS02 accept?
The modules accept an AC input voltage of 100 V to 240 V at 50 Hz or 60 Hz.
What are the output specifications for the DVPPS01 model?
DVPPS01 provides a 24 VDC output with a maximum current of 1 A.