The DVP-04AD-SL is a 4‑channel analog input module for Delta DVP series PLCs. It converts 16‑bit digital data from the PLC into four analog signals, supporting both voltage (‑10 V to +10 V) and current (‑20 mA to +20 mA) inputs.

This guide covers safety and installation precautions, mechanical dimensions, wiring diagrams, electrical specifications, control register descriptions, A/D conversion curve adjustments, error status information, and history command usage. It also provides recommended torque values and cable types for reliable operation.

Read online

Delta DVP04DA-SL specifications

Voltage input range-10 V ~ +10 VDC
Current input range-20 mA ~ +20 mA
Power supply voltage24 VDC (-15% ~ +20%)
Analog input channels4
Resolution16 bits (15 bits effective)
Input impedance< 0.5 Ω
Overall accuracy±0.3 % full scale (25 °C)
Response time per channel250 µs
Isolation voltage500 VDC between analog, digital, and ground

Source: DELTA DVP04DA-SL installation manual(1)

All Delta DVP04DA-SL documents by type

Installation Guide 2

Mounting, wiring and first power-up. Read it before the hardware goes in.

Questions answered in these manuals

What is the recommended tightening torque for the I/O terminal block?

The tightening torque for the I/O terminal block is 1.95 kg‑cm (1.7 in‑lbs).

From: DELTA DVP04DA-SL installation manual(1)

How can the input mode be selected for a channel?

The input mode is set via the channel’s control register (CHx) using values such as 0 for voltage ±10 V, 1 for current ±20 mA, etc.

From: DELTA DVP04DA-SL installation manual(1)

What torque should be used when tightening the I/O terminal block?

The recommended tightening torque is 1.95 kg‑cm (1.7 in‑lbs).

From: Delta DVP04DA-SL Analog Output Module Installation Guide

What safety step must be taken before performing maintenance?

The DC input power must be turned off and you must wait at least one minute before touching any internal circuitry.