Siemens LVL 200E Manuals

ManualLib has 2 documents for the Siemens LVL 200E (sensor): 1 other, 1 user manual. Every file can be read online or downloaded as a PDF for free.

Other 1User Manual 1

Key facts

Brand
Siemens
Model
LVL 200E
Category
sensor
Documents
2
Languages
ES · ZH
Last added
2023-11-24

Start here

ARV 200 - Operating Instructions Vibration for SITRANS LVL200E - Pressure range -1 … 16 bar

ARV 200 - Operating Instructions Vibration for SITRANS LVL200E - Pressure range -1 … 16 bar

User Manual 16 pages · 1.2 MB · ZH

This manual provides assembly, connection, and commissioning information for the ARV 200 vibration clamp-on adapter, which is used with the SITRANS LVL200E level sensor. It covers safety precautions, product description, installation procedures, and maintenance instructions.

The document details the installation process, including tightening torques for the pressure screw and clamping screws, and provides step-by-step instructions for replacing seals and removing the adapter. It also includes technical data and dimensions. This manual is written in Chinese.

Read online

Siemens LVL 200E specifications

Electronic moduleTransistor (NPN/PNP)
Safety Integrity Level (single-channel)SIL2
Safety Integrity Level (multichannel)SIL3
Instrument typeType A
Operating modeLow demand mode, High demand mode
MTBF3.61 x 10^6 h (412 years)
PFDAVG (T1 = 1 year)0.025 x 10^-2
PFH0.030 x 10^-6 1/h
MTTFd3805 years
Performance Level3.00 x 10^-8 1/h (corresponds to e)
Safe state outputTransistors non-conductive (no current)
Ambient temperature correction factor1.3 above 50 C; 2.5 above 60 C
Mean time to repair24 h

Source: Siemens SITRANS LVL 200S, LVL 200E Safety Manual

All Siemens LVL 200E documents by type

User Manual 1

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What safety integrity level can the SITRANS LVL 200S and LVL 200E achieve?

Up to SIL2 in a single-channel architecture and up to SIL3 in a multichannel architecture.

From: Siemens SITRANS LVL 200S, LVL 200E Safety Manual

What is the safe state of the sensor outputs?

The transistors are non-conductive (no current).

From: Siemens SITRANS LVL 200S, LVL 200E Safety Manual

What is the maximum pressure rating for the ARV 200?

The ARV 200 is rated for a pressure range of -1 to 16 bar.

From: ARV 200 - Operating Instructions Vibration for SITRANS LVL200E - Pressure range -1 … 16 bar

What is the required diameter for the tube extension used with the sensor?

The tube extension diameter must be 21.3 mm (0.84 in).

From: ARV 200 - Operating Instructions Vibration for SITRANS LVL200E - Pressure range -1 … 16 bar