Danfoss AK-CC 550A Evaporator Controller User Manual

Danfoss AK-CC 550A Evaporator Controller User Manual

User Manual 36 pages · 3 MB · ES

The Danfoss AK-CC 550A is an evaporator controller for integral control of refrigeration installations and cold rooms. It provides energy optimization, one controller for several refrigeration applications, an integrated front display, quick startup with preset settings, integrated communication resources, and an integrated clock function with a capacitive battery.

Temperature is measured with one or two air temperature sensors before the evaporator (S3) or after it (S4), plus an optional product sensor S6 and an evaporator sensor S5. The controller has an AKV electronic injection valve output and five user-defined relay outputs, and supports day/night thermostat control, adaptive superheat and defrost control, two-compressor control, night curtain and light control, and integrated MODBUS communication with an optional LonWorks card. This manual is written in Spanish.

Read online

Danfoss AK-CC 550 specifications

Supply voltage230 V a.c., 50/60 Hz
Sensor signal S1Pressure transmitter or temperature sensor
Sensor typePt 1000 ohm or PTC 1000 ohm
Cable separation distanceAt least 10 cm
Pressure transmitter receiversUp to 10 controllers

Source: Danfoss AK-CC 550 Controller Instructions

All Danfoss AK-CC 550 documents by type

Questions answered in these manuals

What supply voltage does the Danfoss AK-CC 550 use?

It uses 230 V a.c., 50/60 Hz.

From: Danfoss AK-CC 550 Controller Instructions

How many controllers can receive one pressure transmitter signal?

Up to 10 controllers can receive the signal if there are no significant pressure decreases.

From: Danfoss AK-CC 550 Controller Instructions

Does the controller have an integrated display?

Yes, the controller has an integrated display on its front panel.

From: Danfoss AK-CC 550A Evaporator Controller User Manual

What defrost methods are available?

Defrosting can be natural, electric, or by hot gas.

From: Danfoss AK-CC 550A Evaporator Controller User Manual

What is the Danfoss AK-CC 550A used for?

It is a complete refrigeration control system for refrigerated cabinets and cold rooms, with one controller that can be adapted to different cabinet and room types.

From: Danfoss AK-CC 550A Refrigeration Controller Manual

Which sensors can be used with the AK-CC 550A?

The cabinet temperature is measured with one or two sensors, S3 before the evaporator and S4 after it. An optional S6 product sensor can be placed anywhere in the cabinet, and S5 measures evaporator temperature.

From: Danfoss AK-CC 550A Refrigeration Controller Manual