Key facts
- Brand
- Danfoss
- Model
- VLT Micro FC 51
- Category
- Automation control Equipment
- Industry
- Industrial
- Documents
- 2
- Languages
- EN · ES
- Last added
- 2026-11-19
Start here

Danfoss VLT Micro FC 51 Frequency Converter Quick Guide
This quick guide provides basic safety and installation information for the Danfoss VLT Micro FC 51 frequency converter. It covers high-voltage warnings, leakage current, protective earthing, motor thermal protection, and high-altitude installation.
The document also describes mechanical dimensions, terminal tightening torques, fuse recommendations, mains and motor wiring, control terminal switches, and load sharing or brake connections for frames M1 through M5.
Danfoss VLT Micro FC 51 specifications
| Max supply voltage (IT mains) | 440 V |
|---|---|
| Earth leakage current | Exceeds 3.5 mA |
| DC-link discharge wait (M4-M5) | At least 15 minutes |
| Max cable cross-section (M1-M3) | 4 mm2/10 AWG |
| Max cable cross-section (M4-M5) | 16 mm2/6 AWG |
| Side-by-side clearance | 100 mm above and below |
Source: Danfoss VLT Micro FC 51 Frequency Converter Quick Guide
All Danfoss VLT Micro FC 51 documents by type
The shortest path to a working setup, usually only a few pages.
Questions answered in these manuals
What type of residual current device is required?
Only a Type B (time delayed) RCD shall be used on the supply side.
From: Danfoss VLT Micro FC 51 Frequency Converter Quick Guide
Is the [OFF] key a safety switch?
No. The [OFF] key is not a safety switch and does not disconnect the converter from mains.
From: Danfoss VLT Micro FC 51 Frequency Converter Quick Guide
What is the maximum input voltage for IT (isolated) power supplies?
The maximum allowed input voltage is 440 V.
Is the [Off/Reset] key a safety switch?
No, the [Off/Reset] key is not a safety switch and does not disconnect the converter from the mains.