Danfoss VLT AQUA Drive FC 200 Frequency Converter Application Quick Guide
This Application Quick Guide is for the Danfoss VLT AQUA Drive FC 200 frequency converter. It is intended for trained specialists to use with the product manuals and covers connection, operation via LCP 102, easy commissioning, Profibus DP, fault analysis, and application examples.
The guide includes power and control terminal information, DIP-switch functions, digital input programming options, and safety notes about hazardous voltages and DC-link capacitor discharge. Its examples mainly apply to the basic unit with graphical control panel LCP 102 up to 90 kW (400 V) and initial operation with an asynchronous motor.
Danfoss FC 200 specifications
| Internal +24 V DC source load | 200 mA max. |
|---|---|
| Digital input voltage | 0-24 V DC |
| Digital input logic 0 | < 5 V |
| Digital input logic 1 | > 10 V |
| Analogue inputs | 0-10 V DC or 0/4-20 mA |
| Analogue output | 0/4-20 mA, 500 Ω max. |
| Internal +10 V DC source | 10 V DC, 15 mA max. |
| RS 485 serial interface | 115 kbit/s max. |
| Relay output 1 | 240 V AC, 2 A max. (resistive load) |
| External 24 V power supply | 24 V DC +/- 15% |
| External 24 V power supply input current | 2.2 A max. |
| DC link and brake resistor voltage | 850-1000 V DC max. |
| Earth conductor cross-section | at least 10 mm2 |
| Basic unit power range covered | up to 90 kW (400 V) |
Source: Danfoss VLT AQUA Drive FC 200 Frequency Converter Application Quick Guide
All Danfoss FC 200 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
The shortest path to a working setup, usually only a few pages.
Questions answered in these manuals
What is the drive's ground leakage current?
The drive's ground leakage current exceeds 3.5 mA.
How is motor overload protection set?
Motor overload protection is set by parameter 1-90, Motor thermal protection.
What software version applies to the extended cascade controller option?
The manual applies to extended cascade controller options using software version 1.24.
From: Danfoss VLT AQUA FC 200 Cascade Controller User Manual
How many pumps can the cascade controller control in total?
The cascade controller can control a total of 8 pumps.
From: Danfoss VLT AQUA FC 200 Cascade Controller User Manual
What is the purpose of this manual?
It provides detailed information for the installation and start up of the frequency converter.
Who should install, start up, and maintain the frequency converter?
Installation, start up, and maintenance should be performed by qualified personnel only.