Key facts

Brand
Danfoss
Model
AME 435
Documents
2
Languages
EN
Last added
2026-10-01

Start here

Danfoss AME 335, AME 435 Operating Guide

Danfoss AME 335, AME 435 Operating Guide

User Manual 20 pages · 5 MB · EN

This document is the English operating guide for the Danfoss AME 335 and AME 435 actuators. It provides instructions for mounting, wiring, and configuring the device using DIP switches and jumpers. The guide details various operating modes, including self-stroking for calibration and standby mode for manual control.

Read online

Danfoss AME 435 specifications

Nominal voltage24 V AC/DC
Control input signal0‑20 mA or 0‑10 V
Force400 N
Stroke20 mm
Speed (selectable)7.5 s/mm or 15 s/mm
Maximum medium temperature120 °C
Power consumption (running)4.5 VA
Power supply tolerance±10 %
Output signal range0‑10 V (2‑10 V)
Protection classII
Weight0.45 kg

Source: Danfoss AME 435 QM Actuator Data Sheet

All Danfoss AME 435 documents by type

Datasheet 1

Ratings, dimensions and ordering codes, for selection and design work.

User Manual 1

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

How do I start the automatic calibrating procedure?

Press the STAND BY/RESET button for 5 seconds; the bi‑colour LED will flash green and the actuator will run the calibrating cycle.

From: Danfoss AME 435 QM Actuator Data Sheet

What speed options are available for the actuator?

The actuator can be set to either 7.5 seconds per millimetre or 15 seconds per millimetre via the speed selector switch.

From: Danfoss AME 435 QM Actuator Data Sheet

How do I enter self-stroking mode?

Press and hold the STAND-BY/RESET-button for 5 seconds until the green light starts flashing.

From: Danfoss AME 335, AME 435 Operating Guide

What does a flashing red LED indicate?

It indicates STAND-BY MODE where the actuator is stopped and not responding to the Y signal.

From: Danfoss AME 335, AME 435 Operating Guide