Danfoss AME 335, AME 435 Operating Guide
This document is the English operating guide for the Danfoss AME 335 and AME 435 actuators. It provides instructions for mounting, wiring, and configuring the device using DIP switches and jumpers. The guide details various operating modes, including self-stroking for calibration and standby mode for manual control.
Read onlineDanfoss AME 435 specifications
| Nominal voltage | 24 V AC/DC |
|---|---|
| Control input signal | 0‑20 mA or 0‑10 V |
| Force | 400 N |
| Stroke | 20 mm |
| Speed (selectable) | 7.5 s/mm or 15 s/mm |
| Maximum medium temperature | 120 °C |
| Power consumption (running) | 4.5 VA |
| Power supply tolerance | ±10 % |
| Output signal range | 0‑10 V (2‑10 V) |
| Protection class | II |
| Weight | 0.45 kg |
All Danfoss AME 435 documents by type
Ratings, dimensions and ordering codes, for selection and design work.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
How do I start the automatic calibrating procedure?
Press the STAND BY/RESET button for 5 seconds; the bi‑colour LED will flash green and the actuator will run the calibrating cycle.
What speed options are available for the actuator?
The actuator can be set to either 7.5 seconds per millimetre or 15 seconds per millimetre via the speed selector switch.
How do I enter self-stroking mode?
Press and hold the STAND-BY/RESET-button for 5 seconds until the green light starts flashing.
What does a flashing red LED indicate?
It indicates STAND-BY MODE where the actuator is stopped and not responding to the Y signal.