Key facts
- Brand
- Danfoss
- Model
- ECL Comfort 110
- Category
- Automation control Equipment
- Industry
- Industrial
- Documents
- 2
- Languages
- EN
- Last added
- 2026-11-20
Start here

Danfoss ECL Comfort 110 Controller Data Sheet
The ECL Comfort 110 controller is designed for easy installation with one cable and one connector. It features a custom-designed display with backlight, triac outputs for motorized control valves, relay outputs for pump control, and support for up to four Pt 1000 temperature sensors plus one override input. A room panel or remote control (ECA 60/61) can be connected, and the unit can operate as master or slave in controller systems.
It is prepared for mounting on a DIN rail, a wall or in a panel and is available in 230 V a.c. and 24 V a.c. versions, with or without a timer program. The controller supports weather compensated flow temperature control and constant temperature control, and can be extended with new applications using a chip card and communication interface.
Danfoss ECL Comfort 110 specifications
| Supply voltage (230 V version) | 230 V a.c. - 50 Hz |
|---|---|
| Voltage range (230 V version) | 207 to 244 V a.c. |
| Power consumption | 3 VA |
| Load on relay outputs (230 V) | 4 (2) A |
| Load on triac outputs (230 V) | 15 VA @ 230 V a.c. |
| Supply voltage (24 V version) | 24 V a.c. - 50 Hz |
| Voltage range (24 V version) | 21.6 to 26.4 V a.c. |
| Ambient temperature | 0 - 55 °C |
| Storage temperature | -40 - + 70 °C |
| Enclosure | DIN rail, wall or panel |
| Sensor type | Pt 1000 (1000 Ω @ 0 °C) |
| Grade of enclosure | IP 41 |
| Maximum temperature sensors | 4 Pt 1000 types |
All Danfoss ECL Comfort 110 documents by type
Ratings, dimensions and ordering codes, for selection and design work.
Questions answered in these manuals
What supply voltages are available for the ECL Comfort 110?
The controller is available in 230 V a.c. and 24 V a.c. versions.
How many temperature sensors can be connected?
Up to four Pt 1000 temperature sensors can be connected.
What control applications does the ECL Comfort 110 support?
It supports weather compensated flow temperature control for heating, constant temperature control for domestic hot water, and constant temperature control for DHW on demand.
How many temperature sensors can be connected to the ECL Comfort 110?
Up to four Pt 1000 temperature sensors can be connected.