Danfoss VLT Micro FC 51 frequency converter quick guide covering safety warnings, installation, electrical connections, and control terminals.
This quick guide provides basic safety and installation information for the Danfoss VLT Micro FC 51 frequency converter. It covers high-voltage warnings, leakage current, protective earthing, motor thermal protection, and high-altitude installation.
The document also describes mechanical dimensions, terminal tightening torques, fuse recommendations, mains and motor wiring, control terminal switches, and load sharing or brake connections for frames M1 through M5.
| Max supply voltage (IT mains) | 440 V |
|---|---|
| Earth leakage current | Exceeds 3.5 mA |
| DC-link discharge wait (M4-M5) | At least 15 minutes |
| Max cable cross-section (M1-M3) | 4 mm2/10 AWG |
| Max cable cross-section (M4-M5) | 16 mm2/6 AWG |
| Side-by-side clearance | 100 mm above and below |
Only a Type B (time delayed) RCD shall be used on the supply side.
No. The [OFF] key is not a safety switch and does not disconnect the converter from mains.
The maximum supply voltage allowed when connected to IT mains is 440 V.