Key facts
- Brand
- Siemens
- Model
- RDF410
- Documents
- 3
- Languages
- EN · ZH
- Last added
- 2011-09-21
Start here
Siemens RDF310.2 / RDF310.21 / RDF410.21/CN Room Temperature Controller User Manual
This manual describes the Siemens RDF310.2, RDF310.21 and RDF410.21/CN room temperature controllers, which control room temperature in two-pipe fan coil heating and cooling systems or single-compressor direct expansion cooling systems. It covers operating modes, temperature control, three-speed fan control, valve or compressor output, and commissioning and control parameters.
The RDF310.21 adds LCD backlighting and infrared remote control. The RDF410.21 also includes eight programmable time periods for automatic switching between normal and energy-saving modes, along with moisture protection and fan control settings. This manual is written in Chinese.
Siemens RDF410 specifications
| Working voltage | AC 230 V |
|---|---|
| Heating mode switching deviation | 2 K |
| Cooling mode switching deviation | 1 K |
| Minimum output on time | 1 minute factory setting, adjustable 1 to 10 minutes |
| Fan speed stages | 3 (low, medium, high) |
| Programmable time periods | 8 (RDF410.21) |
| Fan speed change delay | 2 minutes factory setting, adjustable 1 to 5 minutes |
| Installation | In an embedded junction box |
| Display | LCD |
Source: Siemens RDF310.2 / RDF310.21 / RDF410.21/CN Room Temperature Controller User Manual
All Siemens RDF410 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Mounting, wiring and first power-up. Read it before the hardware goes in.
Questions answered in these manuals
What is the recommended mounting location for the thermostat?
The thermostat should be installed in a semi‑flush mounting position as shown in section #223 24 B.
From: SIEMENS RDF310 RDF410 M3067 thermostat installation Manual
What supply voltage does the thermostat require?
The thermostat operates on an AC 230 V supply.
From: SIEMENS RDF310 RDF410 M3067 thermostat installation Manual
What systems can the RDF310.2, RDF310.21 and RDF410.21/CN controllers be used with?
They can control two-pipe fan coil heating and cooling systems or single-compressor direct expansion cooling systems, including cooling-only, heating-only and manual changeover systems.
From: Siemens RDF310.2 / RDF310.21 / RDF410.21/CN Room Temperature Controller User Manual
What additional functions does the RDF310.21 have?
The RDF310.21 adds LCD backlighting and infrared remote control.
From: Siemens RDF310.2 / RDF310.21 / RDF410.21/CN Room Temperature Controller User Manual
How many programmable time periods does the controller support?
The controller provides 8 programmable time periods.
From: Siemens RDF310 / RDF410 Room Temperature Controller User Manual
How can the temperature display unit be changed?
By setting parameter P17 you can switch the display between °C and °F.
From: Siemens RDF310 / RDF410 Room Temperature Controller User Manual