Betet Electronics RCC30 Room Temperature Controller User Manual
The Betet Electronics RCC30 room temperature controller is designed for four-pipe fan coil units. It controls room temperature using a built-in or external sensor and provides switch output signals to valve actuators and a three-speed fan.
The device supports normal, energy-saving, antifreeze, and off operating modes, with remote mode changeover input. Technical data includes an AC230V power supply, a setting range of 8 to 30 °C, and DIP switches for fan control, dead zone, and other parameters. This manual is written in Chinese.
Siemens RCC30 specifications
| Operating voltage | AC230V +10/-15% |
|---|---|
| Frequency | 50/60 Hz |
| Power consumption | Max 6VA |
| Setting range | 8…30 °C |
| Control accuracy | Max ±0.7K at 25 °C |
| Weight | 0.23 kg |
| Protection class | IP30 |
| Fan output rating | AC230V max 600VA |
| Valve output rating | AC230V max 300VA |
Source: Betet Electronics RCC30 Room Temperature Controller User Manual
All Siemens RCC30 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the operating voltage of the RCC30?
The controller operates at AC230V with a tolerance of +10/-15%.
From: Betet Electronics RCC30 Room Temperature Controller User Manual
What operating modes does the RCC30 support?
It supports normal, energy-saving, antifreeze, and off modes.
From: Betet Electronics RCC30 Room Temperature Controller User Manual
How does the RCC30 control heating and cooling valves?
The controller uses output Y11 to open the heating valve when the room temperature falls below the setpoint by half the conversion error and the valve has been fully closed for more than one minute; it closes the valve when the temperature rises above the setpoint by the same margin. The same logic applies to the cooling valve using Y11 (or Y21) with opposite commands.
From: Siemens RCC30 Four-Pipe Fan Coil Temperature Controller Manual
How is fan speed controlled on the RCC30?
Fan speed is controlled by the three outputs Q1, Q2 and Q3. When the “control fan by temperature” function is selected, the fan speed follows the temperature setpoint and operates synchronously with the valve; otherwise it can be set manually.
From: Siemens RCC30 Four-Pipe Fan Coil Temperature Controller Manual