Siemens RCC30 Four-Pipe Fan Coil Temperature Controller Manual

RCC30 is a room temperature controller from Siemens. It can be used for independent room temperature control for four-pipe fan coils for heating and cooling. The control methods include normal, energy-saving and anti-frost modes or off. It outputs switching signals to valve actuators and switching signals to three-speed fans. It can be controlled according to room or return air temperature. The working voltage is AC230V


Brand
Siemens
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
9
File format
PDF
File size
247 KB
Updated
30 September, 2023
Model
RCC30
MD5 checksum
1FB7714800ECC2637BA168C91D972EF6

About this manual

The RCC30 controller regulates room temperature for four‑pipe fan coil units. It can drive heating and cooling valves, control fan speed, and switch between normal, energy‑saving, frost‑protection and standby modes. Sensors may be internal, external room sensors (QAA32) or return‑air sensors (QAH11.1).\n\nInstallation guidelines cover mounting height, wiring practices, DIP switch settings and safety precautions. The document also provides a full wiring diagram, a list of compatible accessories, and detailed technical data such as power ratings, temperature ranges and certification information.

What's inside

  • Introduction
  • Operation Modes
  • Fan Speed Control
  • Heating and Cooling Valve Control
  • Energy Saving and Frost Protection
  • Installation Guidelines
  • Wiring Diagram
  • Technical Data
  • Accessories
  • Certifications and Standards

Specifications

Power supply voltageAC230V ±10/‑15%
Maximum power consumption6 VA
Fan speed output rating (Q1‑Q3)AC230V, max 600 VA
Valve output rating (Y11, Y21)AC230V, max 300 VA
Temperature setting range8 °C … 30 °C
Control accuracy at 25 °C±0.7 K
Heating mode conversion error1 K or 4 K
Cooling mode conversion error0.5 K or 2 K
Operating temperature range-25 °C … +70 °C
Maximum humidity<95 % r.h.
Weight0.23 kg
Enclosure colourWhite (RAL9003)

Frequently asked questions

How does the RCC30 control heating and cooling valves?

The controller uses output Y11 to open the heating valve when the room temperature falls below the setpoint by half the conversion error and the valve has been fully closed for more than one minute; it closes the valve when the temperature rises above the setpoint by the same margin. The same logic applies to the cooling valve using Y11 (or Y21) with opposite commands.

How is fan speed controlled on the RCC30?

Fan speed is controlled by the three outputs Q1, Q2 and Q3. When the “control fan by temperature” function is selected, the fan speed follows the temperature setpoint and operates synchronously with the valve; otherwise it can be set manually.