Danfoss VLT AQUA Drive FC 200 Frequency Converter Application Quick Guide

VLT® AQUA Drive FC 200 frequency converter instruction manual


Danfoss VLT AQUA Drive FC 200 Frequency Converter Application Quick Guide - cover page
Brand
Danfoss
Category
inverter
Document type
Quick Start Guide
Language
English
Pages
40
File format
PDF
File size
1.6 MB
Published
03 November, 2023
Updated
03 November, 2023
Model
FC 200
MD5 checksum
F6FE45AF73B0B05AD3EC0C1528FB1C64

About this manual

This Application Quick Guide is for the Danfoss VLT AQUA Drive FC 200 frequency converter. It is intended for trained specialists to use with the product manuals and covers connection, operation via LCP 102, easy commissioning, Profibus DP, fault analysis, and application examples.

The guide includes power and control terminal information, DIP-switch functions, digital input programming options, and safety notes about hazardous voltages and DC-link capacitor discharge. Its examples mainly apply to the basic unit with graphical control panel LCP 102 up to 90 kW (400 V) and initial operation with an asynchronous motor.

What's inside

  • Connection
  • Power and supply terminals
  • Control terminals
  • DIP switches
  • Digital input programming options
  • Operation via LCP 102
  • Easy commissioning
  • Profibus DP interface
  • Fault analysis
  • Application examples

Specifications

Internal +24 V DC source load200 mA max.
Digital input voltage0-24 V DC
Digital input logic 0< 5 V
Digital input logic 1> 10 V
Analogue inputs0-10 V DC or 0/4-20 mA
Analogue output0/4-20 mA, 500 Ω max.
Internal +10 V DC source10 V DC, 15 mA max.
RS 485 serial interface115 kbit/s max.
Relay output 1240 V AC, 2 A max. (resistive load)
External 24 V power supply24 V DC +/- 15%
External 24 V power supply input current2.2 A max.
DC link and brake resistor voltage850-1000 V DC max.
Earth conductor cross-sectionat least 10 mm2
Basic unit power range coveredup to 90 kW (400 V)

Frequently asked questions

Who is this Application Quick Guide intended for?

It is intended only for trained specialists to use together with the product manuals.

What safety warning applies to the DC link capacitors?

They retain dangerous DC voltages for a very long time after the mains is disconnected, so the specified waiting time must be observed.

What is the maximum load of the internal +24 V DC source?

The internal +24 V DC source has a maximum load of 200 mA.

What is the maximum voltage on analogue inputs 53 and 54?

The maximum voltage on analogue inputs 53 and 54 is 20 V.

Download PDF (1.6 MB)

More Danfoss Manuals