VLT® AQUA Drive FC 200 frequency converter instruction manual
This Application Quick Guide is for the Danfoss VLT AQUA Drive FC 200 frequency converter. It is intended for trained specialists to use with the product manuals and covers connection, operation via LCP 102, easy commissioning, Profibus DP, fault analysis, and application examples.
The guide includes power and control terminal information, DIP-switch functions, digital input programming options, and safety notes about hazardous voltages and DC-link capacitor discharge. Its examples mainly apply to the basic unit with graphical control panel LCP 102 up to 90 kW (400 V) and initial operation with an asynchronous motor.
| Internal +24 V DC source load | 200 mA max. |
|---|---|
| Digital input voltage | 0-24 V DC |
| Digital input logic 0 | < 5 V |
| Digital input logic 1 | > 10 V |
| Analogue inputs | 0-10 V DC or 0/4-20 mA |
| Analogue output | 0/4-20 mA, 500 Ω max. |
| Internal +10 V DC source | 10 V DC, 15 mA max. |
| RS 485 serial interface | 115 kbit/s max. |
| Relay output 1 | 240 V AC, 2 A max. (resistive load) |
| External 24 V power supply | 24 V DC +/- 15% |
| External 24 V power supply input current | 2.2 A max. |
| DC link and brake resistor voltage | 850-1000 V DC max. |
| Earth conductor cross-section | at least 10 mm2 |
| Basic unit power range covered | up to 90 kW (400 V) |
It is intended only for trained specialists to use together with the product manuals.
They retain dangerous DC voltages for a very long time after the mains is disconnected, so the specified waiting time must be observed.
The internal +24 V DC source has a maximum load of 200 mA.
The maximum voltage on analogue inputs 53 and 54 is 20 V.