Phoenix Contact IB IL 24 SEG (-PAC) Inline Segment Terminal Data Sheet

Technical data sheet for the Phoenix Contact IB IL 24 SEG (-PAC) inline segment terminal used to create partial circuits within main circuits.


Phoenix Contact IB IL 24 SEG (-PAC) Inline Segment Terminal Data Sheet - cover page
Brand
Phoenix Contact
Category
Industrial Supply
Document type
Datasheet
Language
English
Pages
5
File format
PDF
File size
199 KB
Published
29 October, 2026
Updated
29 October, 2026
MD5 checksum
158D5DD16278AC7200206E75EF9DBFFD

About this manual

The Phoenix Contact IB IL 24 SEG (-PAC) is an inline segment terminal designed for use within an Inline station. It allows for the creation of a partial circuit (segment circuit) within the main circuit using an external jumper or switch. This terminal does not contain an INTERBUS protocol chip and is not an INTERBUS device. It is intended to be used in conjunction with the IL SYS INST UM E user manual or the Inline system manual.

What's inside

  • Description
  • Ordering Data
  • Technical Data
  • I/O Supply
  • Safety Equipment
  • Local Status Indicators
  • Terminal Point Assignment
  • Internal Circuit Diagram

Specifications

Housing dimensions12.2 mm x 120 mm x 71.5 mm
Weight42 g (without connector); 57.7 g (with connector)
Ambient temperature (operation)-25°C to +55°C
Ambient temperature (storage/transport)-25°C to +85°C
Permissible humidity10% to 95% according to DIN EN 61131-2
Permissible air pressure70 kPa to 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20 according to IEC 60529
Class of protectionClass 3 according to VDE 0106, IEC 60536
Conductor cross-section0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG
Transmission Speed500 kbps or 2 Mbps
Nominal current consumption at UM8.0 A (maximum permissible total current in the potential jumpers UM and US)

Frequently asked questions

Is the IB IL 24 SEG (-PAC) an INTERBUS device?

No, this terminal does not have an INTERBUS protocol chip and therefore is not an INTERBUS device.

What is the connection method for the Inline connector?

The connection method is spring-cage terminals.

What is the function of the green local status indicator?

The green indicator identifies 24 V supply in the segment circuit US.