This document describes the XT110C-111C-D SP R.1.1 30.08.2013 XT110C - XT111C - XT110D - XT111D 1/4 single-stage digital controller with multi-probe input.
This Spanish-language manual covers the Dixell XT110C, XT111C, XT110D and XT111D, single-stage ON/OFF digital controllers in DIN rail format for temperature, humidity and pressure applications with direct or inverse action selectable by the user. The analog input type can be set by parameter depending on the model: PTC or NTC probes; PTC, NTC, Pt100 and J, K, S thermocouples; or 4÷20mA, 0÷1V and 0÷10V signals.
The document explains first installation and probe configuration, front panel commands and LED functions, viewing and changing the setpoint, the user parameter list Pr1 and the configuration list Pr2 (protected by security code 321), probe measuring ranges, the parameter list for regulation and alarms, installation and mounting, electrical and serial connections, use of the HOTKEY programming key, digital input, alarm signals, technical data and default values. This manual is written in Spanish.
| NTC probe range | -40°C / -40°F to 110°C / 230°F |
|---|---|
| PTC probe range | -50°C / -58°F to 150°C / 302°F |
| Pt100 probe range | -200°C / -328°F to 600°C / 1112°F |
| TcK thermocouple range | 0°C / 32°F to 1300°C / 1999°F |
| TcJ thermocouple range | 0°C / 32°F to 600°C / 1112°F |
| TcS thermocouple range | 0°C / 32°F to 1400°C / 1999°F |
| Anti-short cycle delay (AC) | 0÷250 s |
| Alarm delay (ALd) | 0÷999 min |
Enter the programming menu by pressing SET+DOWN for 3 seconds, select the PbC parameter and press SET, choose the probe type, confirm with SET, then switch the controller off and on again.
The security code is 321, entered after the flashing "PAS" message appears when accessing Pr2.
Hold both the UP and DOWN buttons for more than 3 seconds; "POF" is displayed and the keyboard locks, and holding both buttons again until "Pon" appears unlocks it.
Hold the SET key for 3 seconds, change the value with the UP or DOWN buttons within 10 seconds, then press SET again or wait 10 seconds to store the new value.