Key facts
- Brand
- dixell
- Model
- XT110C
- Category
- Automation control Equipment
- Documents
- 2
- Languages
- ES · ZH
- Last added
- 2023-11-12
Start here

Dixell XT110C XT111C Temperature/Humidity/Pressure Controller User Manual 1592002211
Published as document 1592002211, this Chinese manual covers the Dixell XT110C and XT111C single-stage universal interchangeable electronic controllers for temperature, humidity, or pressure. It explains safety precautions, probe setting during first installation, front-panel keys and LED indicators, and the Pr1/Pr2 parameter levels.
The manual also lists probe types and measurement ranges, parameter descriptions, mounting and electrical connection methods, serial communication and programming-key use, digital inputs, alarm behavior for the XT111C, technical specifications, wiring diagrams, and default settings. This manual is written in Chinese.
Dixell XT110C specifications
| NTC probe range | -40°C / -40°F to 110°C / 230°F |
|---|---|
| PTC probe range | -50°C / -58°F to 150°C / 302°F |
| Pt100 probe range | -200°C / -328°F to 600°C / 1112°F |
| TcK thermocouple range | 0°C / 32°F to 1300°C / 1999°F |
| TcJ thermocouple range | 0°C / 32°F to 600°C / 1112°F |
| TcS thermocouple range | 0°C / 32°F to 1400°C / 1999°F |
| Anti-short cycle delay (AC) | 0÷250 s |
| Alarm delay (ALd) | 0÷999 min |
All Dixell XT110C documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
How do I set the probe type on the XT110C/XT111C/XT110D/XT111D?
Enter the programming menu by pressing SET+DOWN for 3 seconds, select the PbC parameter and press SET, choose the probe type, confirm with SET, then switch the controller off and on again.
What is the security code for the Pr2 parameter list?
The security code is 321, entered after the flashing "PAS" message appears when accessing Pr2.
How do I enter the Pr2 parameter level on the XT110C/XT111C?
Enter the Pr1 level, select Pr2, and enter the safety password 321 when prompted.
From: Dixell XT110C XT111C Temperature/Humidity/Pressure Controller User Manual 1592002211
What current and voltage input signals does the controller accept?
It accepts 4–20 mA, 0–1 V, and 0–10 V signals according to the probe setting options.
From: Dixell XT110C XT111C Temperature/Humidity/Pressure Controller User Manual 1592002211