User manual for the DIXELL XH260L-V microprocessor controller that regulates temperature and humidity in refrigeration systems.
This manual covers the XH260L (38x185 mm) and XH260V (100x64 mm) microprocessor controllers, which are used in medium- or low-temperature refrigeration systems and can control humidity and temperature at the same time. Six relay outputs drive the compressor, heater, defrost, evaporator fan, dehumidifier and humidifier; two NTC sensor inputs measure temperature and the defrost end temperature, one 4-20 mA analog input adjusts humidity, and one digital input (dry contact) has a function set by parameter. Parameters can be copied with the hot-key programming function.
The manual explains neutral-zone temperature control of the compressor and heater, the two defrost types (electric or hot gas) and defrost modes, humidity control with or without a dehumidifier relay, fan operating modes set by parameter FnC, the display, keys and indicator LEDs, the Pr1 and Pr2 parameter levels (password 321), keypad locking, and the parameter table. It also states that a faulty controller should be described in detail and returned to the dealer or to the DIXELL headquarters in Italy. This manual is written in Chinese.
| XH260L dimensions | 38 x 185 mm |
|---|---|
| XH260V dimensions | 100 x 64 mm |
| Relay outputs | 6 relay outputs (compressor, heater, defrost, evaporator fan, dehumidifier, humidifier) |
| Temperature sensor inputs | 2 NTC inputs (one for temperature, one for defrost end temperature) |
| Humidity input | 1 analog input 4-20 mA for humidity control |
| Digital input | 1 digital input, passive dry contact, function set by parameter |
| Lowest temperature set point (LS) | -50.0 °C up to the temperature set point |
| Highest temperature set point (US) | set point up to 110 °C |
| Humidity set point limits (LSH/USH) | LSH from Lci to Set H; USH from Set H to uci |
| Defrost interval (IdF) | 1 to 120 hours |
Enter Pr1 first, select the Pr2 parameter and press the Set key, then type the safety password 321. Alternatively, press the Set + key combination within 30 seconds of switching the controller on.
Press the defrost key for more than 2 seconds to start a manual defrost.
It cancels humidity control, so the controller controls temperature only.
They are selected with parameter FnC: C-n and O-n keep the fan off during defrost, while C-y and O-y keep it running during defrost.
tdF selects electric defrost (rE), where the compressor stops during defrost, or hot gas defrost (in), where the compressor and defrost relay both run.