Tyco LIM800 MX addressable loop line isolator module: features, specifications, mounting, wiring and termination details.
This two-page leaflet from Tyco Fire Protection Products covers the LIM800, an MX Addressable Loop Isolator Module used to provide short circuit isolation between zones or portions of an MX addressable loop. It explains how LIM800s are placed around the loop to monitor loop voltage either side of the device, and how the electronic switches open to isolate a shorted section so the rest of the loop can still be driven by the MX Control and Indicating Equipment (CIE). The additional spur output, the yellow LED indication, and the 100 IB unit load supported on each connection are also described.
The document lists the LIM800 specifications (loop voltage, input current, series resistance, equivalent capacitance, IB units, temperatures, humidity, dimensions and wire size), part numbers for the module and its ancillary cover, back box and housing, and the ActivFire and FPANZ listings. Mounting options are described, including fitting to a gearplate with plastic standoffs, an M520 Ancillary Cover with K2142 back box, or a D800 Ancillary Housing, together with the L+, L–, S+, S–, R+ and R– wiring and termination designations.
| Loop Voltage | 20V to 40Vdc |
|---|---|
| Input Current (normal) | 80μA |
| Input Current (tripped, max.) | 10mA |
| Series Resistance (max.) | 0.25 Ohm |
| Equivalent Capacitance | 0.5nF |
| IB Units between Isolator | 100 (max.) |
| Max. LIM800 per Loop | 200/250 |
| Ambient Temperature | –25°C to +70°C |
| Storage Temperature | –40°C to +80°C |
| Relative Humidity | 10% to 95% (non cond.) |
| Dimensions (HWD) | 61 x 84 x 14 mm |
| Wire Size (maximum) | 2.5 sq. mm |
| Part Numbers | 545.800.004 LIM800; 517.035.010 K2142 Back Box; 557.201.401 D800 Ancillary Housing |
| Listings | ActivFire afp-1446; FPANZ VF/657 |
It is an MX Addressable Loop Isolator Module that can be used to provide short circuit isolation between zones or portions of the MX addressable loop.
It supports up to 100 IB units of MX load on each connection, so additional LIM800s can be installed on long cable sections.
It is supplied as an open circuit board with mounting hardware and must be fitted into a suitable enclosure, such as on a gearplate with plastic standoffs, an M520 Ancillary Cover with K2142 back box, or a D800 Ancillary Housing.
The module includes a yellow LED that indicates when one of its connections is shorted.