Delta's VFD-EL series of multifunctional mini AC motor drives are made with high-quality components and materials and the latest in microcomputer control technology.
This is the user manual for the Delta VFD-EL series multifunctional mini AC motor drive. It explains how to install and wire the drive, operate it from the digital keypad, set its parameter groups, diagnose faults such as overcurrent (OC), overvoltage (OV) and overload (OL), and perform periodic inspection and maintenance. The series is intended for variable-speed control of three-phase induction motors and must be installed and serviced by qualified electrical personnel.
The manual describes the product appearance, nameplate and model numbering (e.g. VFD007EL23A), frame sizes A and B, and the main-circuit and control-circuit terminals. Appendices cover standard specifications, optional accessories such as braking resistors, reactors, the RC-01 remote operator, the PU06 communication interface operator and CME-DN01/CME-LW01/CME-PD01 communication modules, and how to select a suitable drive. This edition applies to firmware v1.14. This manual is written in Chinese.
| Frame A capacity range | 0.25–2 hp (0.2–1.5 kW) |
|---|---|
| Frame B capacity range | 1–5 hp (0.75–3.7 kW) |
| Applicable motor | Three-phase induction motors only |
| Power supply voltage limit | 240 V for 230V series (120 V for 115V series, 480 V for 460V series) |
| Maximum power supply current | 5000 A RMS |
| Storage temperature | -20 °C to +60 °C |
| Storage humidity | 0% to 90% RH, non-condensing |
No. The series is designed for variable-speed operation of three-phase induction motors and must not be used for single-phase motors or other purposes.
Only after the AC power has been cut and the READY indicator has gone out; before that, dangerous high voltage remains inside the drive.
Terminal E must be correctly grounded: class-3 grounding for the 230V series and special grounding for the 460V series.
From the Delta website at http://www.delta.com.tw/industrialautomation/.