Delta GFMS-RM01S/GFDI-RM01N/GFDO-RM01N/GFPS-0202/GFPS-0303/0170-0101 Modbus RTU Connection Operating Manual

This document is about Delta PLC Modbus RTU Connection Operation Manual, it introduces how to use ISPSoft program to connect Delta PLC with Modbus RTU.


Delta GFMS-RM01S/GFDI-RM01N/GFDO-RM01N/GFPS-0202/GFPS-0303/0170-0101 Modbus RTU Connection Operating Manual - cover page
Brand
Delta
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
9
File format
PDF
File size
731 KB
Published
09 November, 2023
Updated
09 November, 2023
MD5 checksum
8AFB989E401A3064D4D43EFEDA91E5C8

About this manual

This manual lists the remote I/O module system configuration, including the master, digital input, digital output, power, and interface modules, and describes the interface module's role in converting Delta PLC RS-485 communication to an RJ45 connection.

It also explains the Delta PLC hardware connection and ISPSoft communication setup, including COM2 RTU settings and the MODRW command for reading and writing I/O module registers.

What's inside

  • Remote I/O Module System Configuration List
  • Product Description
  • Delta PLC Connection Setup
  • Delta PLC Hardware Connection
  • Programming Example

Specifications

COM2 communication modeRTU mode
COM2 baud rate115200 bps
COM2 data format8 data bits, no parity, 1 stop bit
First GFDI-RM01N register address1000(HEX)
First GFDO-RM01N register address2000(HEX)

Frequently asked questions

What COM2 communication settings are required?

Use RTU mode at 115200 bps with 8 data bits, no parity, and 1 stop bit.

Which command sets up reading and writing of the I/O module?

Use the MODRW command.

What register address is used for the first GFDI-RM01N?

The first GFDI-RM01N uses register address 1000(HEX).

What register address is used for the first GFDO-RM01N?

The first GFDO-RM01N uses register address 2000(HEX).