This document is about Delta PLC Modbus RTU Connection Operation Manual, it introduces how to use ISPSoft program to connect Delta PLC with Modbus RTU.
This manual lists the remote I/O module system configuration, including the master, digital input, digital output, power, and interface modules, and describes the interface module's role in converting Delta PLC RS-485 communication to an RJ45 connection.
It also explains the Delta PLC hardware connection and ISPSoft communication setup, including COM2 RTU settings and the MODRW command for reading and writing I/O module registers.
| COM2 communication mode | RTU mode |
|---|---|
| COM2 baud rate | 115200 bps |
| COM2 data format | 8 data bits, no parity, 1 stop bit |
| First GFDI-RM01N register address | 1000(HEX) |
| First GFDO-RM01N register address | 2000(HEX) |
Use RTU mode at 115200 bps with 8 data bits, no parity, and 1 stop bit.
Use the MODRW command.
The first GFDI-RM01N uses register address 1000(HEX).
The first GFDO-RM01N uses register address 2000(HEX).