SMC EX12*-STA1-XP Series SI Unit Installation and Maintenance Manual

This manual provides installation and maintenance instructions for OMRON EX12*-STA1-XP series products.


SMC EX12*-STA1-XP Series SI Unit Installation and Maintenance Manual - cover page
Brand
SMC
Category
Automation control Equipment
Document type
Installation Guide
Language
English
Pages
1
File format
PDF
File size
205 KB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
BC7CB1F7C60BE5837D072CB993F42EF0

About this manual

The manual covers the SMC EX12*-STA1-XP Series SI unit, which connects to an OMRON SYSMAC C (CV) Series SYSBUS wire system. It states that the unit has 16 output points and that up to 512 I/O points (32 stations) can be used per PLC master unit.

It lists specifications, applicable PLC master units C500-RM201 and C200H-RM201, and applicable solenoid valve series for each model. Installation content includes terminal block connections, wiring notes, LED indications, address setting from 0 to 31, Hold/Clear setting, and end station setting.

What's inside

  • Safety Instructions
  • Specifications
  • Applicable PLC
  • Applicable solenoid valves
  • Terminal block
  • Wiring
  • LED display
  • Address setting
  • Hold/Clear setting
  • End station setting

Specifications

Output points16 points
Output styleTransistor style (NPN open collector style)
Connecting loadDC24V, solenoid valve with lamp-surge voltage protection circuit of 2.1W or less
Residual voltage0.4V or less
Power supply voltageDC24V +10%, -5%
Current consumption0.3A or less (inside unit)
Weight170g (EX120-STA1-XP), 190g (EX121-STA1-XP), 180g (EX122-STA1-XP)
Operating ambient temperature0~+50°C
Operating ambient humidity35~85%RH (no dew allowed)
Protection classIP40

Frequently asked questions

Which PLC master units are required for the SYSBUS wire system?

The manual lists the C500-RM201 and C200H-RM201 as the master units required to operate the SYSBUS wire system.

Which solenoid valves are applicable to the EX120-STA1-XP?

The EX120-STA1-XP is listed for VQ1000 and VQ2000 solenoid valves.

What is the address setting range on the SI unit?

The address setting range is 0 to 31, set with the address setting switch.

What does the ERR LED indicate?

The ERR LED lights for abnormal transmission.