DPM-C501L is a multi-functional intelligent electric meter for various industries' power distribution (power system) monitoring and control.
The Delta DPM-C501L is a multi-function control intelligent electric meter for power distribution monitoring and control in various industries, and it is suitable for measuring CAT III power systems. This user manual covers the product overview, appearance and display, safety warnings, electrical and communication specifications, operation interface, dimensions, and current transformer accessories. This manual is written in Chinese.
| Rated Voltage | Line voltage: 35 to 690 VAC (L-L); phase voltage: 20 to 400 VAC (L-N) |
|---|---|
| Rated Current | 1 A / 5 A |
| Frequency | 50/60 Hz |
| Power Supply | 80 to 265 VAC (maximum power consumption 4.6 W), 100 to 300 VDC |
| Communication | RS-485, MODBUS-RTU, 9600 / 19200 / 38400 bps |
| Dimensions (W x H x D) | 96 x 96 x 91.8 mm |
| IP Protection | IP52 (front panel), IP20 (meter body) |
| Operating Temperature | -20 °C to +50 °C (-4 °F to +122 °F) |
| Voltage and Current Accuracy | ±0.5% |
The manual states a line voltage range of 35 to 690 VAC (L-L) and a phase voltage range of 20 to 400 VAC (L-N).
It uses an RS-485 interface with MODBUS-RTU and supports 9600, 19200, and 38400 bps.
The dimensions are 96 x 96 x 91.8 mm (width x height x depth).
The front panel is rated IP52 and the meter body is rated IP20.