SMC IP8000-0∗0-∗-X14 IP8100-0∗0-∗-X14 Electro-Pneumatic Positioner Manual

This document is the manual of IP8000-0∗0-∗-X14, IP8100-0∗0-∗-X14 electro-pneumatic positioner.


SMC IP8000-0∗0-∗-X14 IP8100-0∗0-∗-X14 Electro-Pneumatic Positioner Manual - cover page
Brand
SMC
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
39
File format
PDF
File size
4 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
1CA3FB35218415B042BE9FADAE2EBC44

About this manual

The SMC IP8000/IP8100 Series electro-pneumatic positioner controls the motion of an actuator by the operation of a pilot valve, which is activated by signal current from an adjustment unit mounted to an air cylinder. The -X14 versions received intrinsically safe explosion proof certification conforming to the ATEX directive (Ex ib IIC T5/T6 Gb) from DEKRA.

The manual covers the lever-type IP8000 and the rotary/cam-type IP8100 and gives specifications, operation principle, attaching, piping with the internal feedback unit, electrical wiring, adjustment, maintenance and check, troubleshooting, options and ordering information.

What's inside

  • Safety Instructions
  • Outline
  • Specifications
  • Operation Principle
  • Attaching
  • Piping and Attaching of Internal Feedback Unit
  • Electrical Wiring
  • Adjustment
  • Maintenance and Check
  • Troubleshooting

Specifications

Input current4 to 20 mADC (standard)
Input resistance235 ±15 Ω (4 to 20 mADC)
Supply air pressure0.14 to 0.7 MPa
Output flow rate80 l/min (ANR) or more at SUP = 0.14 MPa
Air consumptionWithin 5 l/min (ANR) at SUP = 0.14 MPa
Ambient and fluid temperature (-X14)-20 to 80 °C (T5); -20 to 60 °C (T6)
Explosion protectionIntrinsic safety type; 0344 II2G Ex ib IIC T5/T6 Gb
Air connection port1/4 NPT female screw
Body materialAluminum diecast
WeightApprox. 2.4 kg
Degree of protectionJISF8007 IP65 (conforms to IEC Pub.529)
Current circuit parametersUi ≤ 28 V, Ii ≤ 125 mA, Pi ≤ 1.2 W, Ci ≤ 0 nF, Li ≤ 0 mH

Frequently asked questions

What is the standard input current of the IP8000/IP8100 positioner?

The standard input current is 4 to 20 mADC. A 1/2 split range is possible with the standard type by adjusting the span.

What supply air pressure does the positioner require?

The supply air pressure range is 0.14 to 0.7 MPa.

What is the air connection port size?

The air connection port is a 1/4 NPT female screw.

What ATEX certification do the -X14 models have?

They are intrinsically safe explosion proof conforming to the ATEX directive, with marking 0344 II2G Ex ib IIC T5/T6 Gb, certified by DEKRA.

Download PDF (4 MB)