Instruction manual for ICT DIN series power supply
The ICT DIN Series Power Supply instruction manual covers the ICT360-24DIN and ICT360-48DIN models. The units provide 360 watts of 24- or 48-volt DC output and include integrated battery charging, a low voltage disconnect relay, a wide-range AC input, Form C alarm contacts, and an RJ11 serial port for communication with an ICT-DIN-PDU6 power distribution unit.
The manual describes installation on a TS-35 (EN5002) DIN rail, wiring for load, battery, alarm and temperature sensor connections, operation with a backup battery, status indicators and alarms, and product specifications. It includes safety warnings, battery backup guidance, LVD setpoints, and selectable charge current settings.
| Output Power | 360 W of 48 V or 24 V DC output |
|---|---|
| ICT360-24DIN Output | 27.6 V, 15 A maximum, 13.5 A continuous |
| ICT360-48DIN Output | 55.2 V, 7.5 A maximum, 6.5 A continuous |
| AC Input | 120 Vac or 240 Vac, 50/60 Hz |
| Battery Type | Lead-Acid |
| Battery Charge Current Settings | 25%, 50%, 75%, or 100% of available output current |
| Battery Charge Current Default | 25% |
| LVD Disconnect Default | 22 V for 24 V setting; 44 V for 48 V setting |
| LVD Reconnect Default | 25 V for 24 V setting; 50 V for 48 V setting |
| Integrated Battery Fuse | 20 A |
| DIN Rail Standard | TS-35 (EN5002) |
| Minimum Clearance | 4 inches above and below |
It provides 360 watts of 48- or 24-volt DC output.
Use only a Lead-Acid battery with a rating and capacity appropriate for the power supply model.
Rotate the CHARGE CURRENT selector dial with a slotted screwdriver.
The default disconnect voltage is 22 V for the 24 V setting and 44 V for the 48 V setting.