ICT DIN Series Power Supply ICT360-24DIN / ICT360-48DIN Instruction Manual

Instruction manual for ICT DIN series power supply


ICT DIN Series Power Supply ICT360-24DIN / ICT360-48DIN Instruction Manual - cover page
Brand
ICT
Category
AC-DC Power
Document type
User Manual
Language
English
Pages
14
File format
PDF
File size
884 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
8954566ED7123627141903A5FB2DD8FF

About this manual

The ICT DIN Series Power Supply instruction manual covers the ICT360-24DIN and ICT360-48DIN models. The units provide 360 watts of 24- or 48-volt DC output and include integrated battery charging, a low voltage disconnect relay, a wide-range AC input, Form C alarm contacts, and an RJ11 serial port for communication with an ICT-DIN-PDU6 power distribution unit.

The manual describes installation on a TS-35 (EN5002) DIN rail, wiring for load, battery, alarm and temperature sensor connections, operation with a backup battery, status indicators and alarms, and product specifications. It includes safety warnings, battery backup guidance, LVD setpoints, and selectable charge current settings.

What's inside

  • Product Description
  • Installation
  • Wiring
  • Operation
  • Status Indicators and Alarms
  • Product Specifications

Specifications

Output Power360 W of 48 V or 24 V DC output
ICT360-24DIN Output27.6 V, 15 A maximum, 13.5 A continuous
ICT360-48DIN Output55.2 V, 7.5 A maximum, 6.5 A continuous
AC Input120 Vac or 240 Vac, 50/60 Hz
Battery TypeLead-Acid
Battery Charge Current Settings25%, 50%, 75%, or 100% of available output current
Battery Charge Current Default25%
LVD Disconnect Default22 V for 24 V setting; 44 V for 48 V setting
LVD Reconnect Default25 V for 24 V setting; 50 V for 48 V setting
Integrated Battery Fuse20 A
DIN Rail StandardTS-35 (EN5002)
Minimum Clearance4 inches above and below

Frequently asked questions

What output power does the ICT DIN Series power supply provide?

It provides 360 watts of 48- or 24-volt DC output.

What type of battery should be connected?

Use only a Lead-Acid battery with a rating and capacity appropriate for the power supply model.

How is the battery charge current adjusted?

Rotate the CHARGE CURRENT selector dial with a slotted screwdriver.

What are the default low voltage disconnect setpoints?

The default disconnect voltage is 22 V for the 24 V setting and 44 V for the 48 V setting.

Download PDF (884 KB)

More ICT Manuals


View all ICT manuals →