AX-3 series quick start guide introduces the basic functions and usage methods of AX-3 series PLC.
This quick start guide for the Delta AX-3 Series PLC explains how to get the system up and running quickly. It introduces the system architecture and how the host operates, including tasks, task types, multi-task execution and the watchdog, then walks through building a standard PLC project: preparing hardware and software, installing modules and removable terminals, wiring the PLC power module, powering up, and creating a project, hardware configuration, global symbols, function blocks and the main program in DIADesigner-AX.
The second half covers motion control projects, with step-by-step procedures for an EtherCAT servo axis, a Pulse Out servo axis, a virtual axis used as a synchronous master, and a built-in encoder used as a synchronous master, plus program monitoring, device-to-computer connection settings and oscilloscope trace monitoring. The third edition uses the AX-324N as its example model. This manual is written in Chinese.
| Minimum system configuration | One host module plus one power module |
|---|---|
| Maximum expansion modules | 32 (excluding power and host modules) |
| I/O data capacity | IN: 8,192 bytes / OUT: 8,192 bytes |
| Example model used in the guide | AX-324N |
At least one host module and one power module are required before the system can be planned and operated.
Up to 32 expansion modules, not counting the power and host modules; exceeding a limit causes the host to issue an alarm.
The guide refers to DIADesigner-AX for installation and programming, and there is a separate DIADesigner-AX user manual.
If any one of the three limit conditions is exceeded, the host will send an alarm message.