Magnetic scale installation guide.
This manual provides instructions for installing and operating the WayCon Magnetic Scale Series MXW11 and MXW21. It details safety precautions, mechanical mounting requirements including specific gap tolerances, and electrical connection procedures to ensure proper signal transmission.
The document also covers output signals such as index and reference pulses, maintenance recommendations for keeping the sensor system clean, and a troubleshooting section for common faults like inaccurate measurements or lack of pulse output.
| Recommended tightening torque | 1.1 Nm |
|---|---|
| Minimum bend radius of the cable | R ≥ 42 mm |
| Index pulse duration | 70 electrical degrees ± 10° |
| Reference signal amplitude (RS422) | according to RS-422 |
| Reference signal amplitude (1Vpp code) | 1 Vpp |
The yaw must be less than 3°, tilt less than 1°, lateral deviation ±1.5 mm, roll less than 3°, and the gap between sensor and scale should be 0.1...0.5 mm.
The yaw must be less than 3°, tilt less than 1°, lateral deviation ±1.5 mm, roll less than 3°, and the gap between sensor and scale should be 0.1...1 mm.
No, you must avoid using strong magnets on or near the unit to guarantee correct working of the device.