Delta CME-PD01 Profibus Communication Module User Manual


Delta CME-PD01 Profibus Communication Module User Manual - cover page
Brand
Delta
Category
Communications equipment
Document type
User Manual
Language
English
Pages
35
File format
PDF
File size
529 KB
Published
23 December, 2011
Updated
17 October, 2026
MD5 checksum
A2DC8B4425C0572EBB2447E0FD831569

About this manual

The Delta CME-PD01 is a communication module that links VFD-E series AC drives to a PROFIBUS-DP network. It features a DB9 PROFIBUS-DP interface, an RJ-45 RS-485 port for drive connection, two status LEDs, and rotary address switches for node configuration.

The manual covers receiving and inspection, product overview with layout and technical information, PROFIBUS and PROFIBUS-DP introduction, installation and pin assignment, communication settings including address, parameters, cyclical data, and PKW access, GSD file parameter configuration, troubleshooting with LED diagnostics and error codes, and mechanical dimensions.

What's inside

  • Preface
  • Overview
  • Profibus Introduction
  • Installation Information
  • Communication
  • Parameters Setting in GSD file
  • Troubleshooting
  • Dimensions

Specifications

Supported baud rates9.6 kbaud to 12 Mbaud
Status LEDsSP LED (drive link), NET LED (PROFIBUS link)
Address settingTwo rotary switches ADDH (high 4 bits) and ADDL (low 4 bits)
Drive interfaceRS-485 (RJ-45), 8-pin cable, 15 V DC supplied by VFD-E
Data exchangeCyclical PZD and PKW parameter access, SYNC/FREEZE support
Dimensions57.3 × 59.7 × 3.6 mm (approx.)

Frequently asked questions

What baud rates does the CME-PD01 support?

The module supports baud rates from 9.6 kbaud up to 12 Mbaud.

How is the PROFIBUS node address configured?

The address is set with two rotary switches: ADDH for the high 4 bits and ADDL for the low 4 bits.

What do the SP and NET LEDs indicate?

SP LED shows the connection status between the module and the VFD-E drive; NET LED shows the connection status between the module and the PROFIBUS-DP network.

How is the CME-PD01 powered?

It receives 15 V DC from the VFD-E drive through the 8-pin RJ-45 communication cable.