The Delta DVP-SS series is a compact programmable logic controller (PLC) featuring an MPU with 14 points, RUN/STOP switches, and support for 8 to 16 points of extension, reaching a maximum of 128 I/O points. It is designed for various applications involving different I/O points, power types, output modules, and A/D or D/A conversion.

This open-type PLC requires installation in an enclosure to protect it from dust, humidity, and vibration. The power unit is separate from the MPU to facilitate easy installation and a compact footprint.

What's inside

  • Introduction
  • Product Profile and Outline
  • Electrical Specifications
  • Model Name & I/O Configuration
  • PLC Mounting Arrangements and Wiring Notes
  • Power Input Wiring
  • Safety Wiring
  • Input Point Wiring
  • Output Point Wiring

Specifications

Power supply voltage24V DC (-15%~20%)
Power Consumption3.5W
Operating Temperature0°C ~ 55°C
Maximum I/O points128 points
Input Current5mA at 24V DC

Frequently asked questions

How should the DVP-SS PLC be mounted?

It can be secured to a cabinet using a DIN rail that is 35mm in height and 7.5mm in depth.

What happens if the power input is lower than 20.4V DC?

The PLC will stop operation, outputs will turn OFF, and the ERROR LED will blink swiftly.

What wire specifications are recommended for I/O wiring?

Use 22-16AWG (1.5mm) single-core bare wire or multi-core wire.