Installation manual for the YASKAWA PG-F3 EnDat encoder option card, covering components, electrical installation, parameters, troubleshooting, and…
This manual describes the YASKAWA PG-F3, an Encoder Type (EnDat) option card for YASKAWA AC drives. The card uses HEIDENHAIN rotary encoders EnDat2.1/01 and EnDat2.2/01; when installed on the drive's control board, the drive uses the encoder feedback signal to detect motor speed and maintain constant motor speed by adjusting output frequency in response to load changes. The PG-F3 requires the drive to use Closed Loop Vector Control for PM and accepts a maximum input frequency of 50 kHz.
The manual covers package contents and required tools, option card components and terminal block connections, electrical installation safety messages, the related drive parameters, troubleshooting, and product specifications.
| Supported encoder types | HEIDENHAIN rotary encoders EnDat2.1/01 and EnDat2.2/01 |
|---|---|
| Maximum input frequency | 50 kHz |
| Encoder power supply | 5 V ± 5% at 330 mA or 8 V ± 10% at 150 mA |
| Data signal level | RS-485 protocol |
| B pulse monitor output | Line driver, RS-422 level, resolution 1/n |
| Required control mode | Closed Loop Vector Control for PM |
The PG-F3 uses HEIDENHAIN rotary encoders EnDat2.1/01 and EnDat2.2/01.
The PG-F3 has a maximum input frequency of 50 kHz, and the input frequency must not exceed 50 kHz during operation.
The drive must use Closed Loop Vector Control for PM to operate the motor with the PG-F3.