This supplement provides updated safety messages, receiving information, UL/CSA standards compliance, and drive derating data for Yaskawa A1000 and P1000 AC…
This manual supplement (TOEP YEASUP 03) updates the Quick Start Guides and Technical Manuals for Yaskawa A1000 High Performance Vector Control Drives and P1000 Industrial Fan and Pump Drives. It replaces or adds to sections covering safety messages, nameplate information, installation environment, dimensions, drive derating data, and UL/CSA standards compliance.
The supplement includes revised safety warnings about short-circuit current ratings, a table of applicable drive models across 200 V, 400 V, and 600 V classes, and detailed factory-recommended branch circuit protection specifications (MCCB, time-delay fuses, non-time-delay fuses, and Bussman semiconductor fuses) for both Normal Duty and Heavy Duty operating modes.
| Short-Circuit Current Rating | 100,000 RMS symmetrical amperes |
|---|---|
| UL Standard | UL508C |
| Recommended Branch Circuit Protection | Semiconductor protective type fuses preferred |
| Applicable Voltage Classes | 200 V, 400 V, 600 V |
The drives are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes.
The drives are tested in accordance with UL Standard for Safety UL508C.
Yaskawa recommends semiconductor protective type fuses (Bussman FWH for 240 V/480 V models, FWP for 600 V models).