Information sheet for Tyco T614 Mk2 collective heat detectors, including specifications, installation, maintenance, and application notes.
Tyco T614 Mk2 heat detectors use a fast-response thermistor-based design to identify when ambient temperature exceeds a fixed threshold. Type A and Type C detectors also provide rate-of-rise detection by comparing two thermistors with different thermal responses.
The detectors include a built-in diode on the remote indicator output, may be intermixed with Minerva and Tyco 614 detectors, and are compatible with Tyco F3200, 4100U, and MX4428 c.i.e. The sheet also covers installation, maintenance, locking device use, wiring, and detector selection guidance.
| Height | 53 mm |
|---|---|
| Diameter | 127 mm |
| Mass | 174 g |
| Compatible bases | 5B, MUB (M614) |
| Operating voltage | 11 Vdc to 32 Vdc |
| Quiescent current | 85 µA @ 24 Vdc |
| Alarm state current | 5 mA to 80 mA |
| Alarm state voltage | 3 V to 12.4 V |
| Remote indicator | Tyco E500 Mk2 |
| Environmental use | Indoor applications only |
| Part numbers | T614A, T614B, T614C, T614D |
| Storage temperature | -10°C to +75°C |
| Relative humidity | 10% to 95% (non-condensing) |
| CSIRO ActivFire listing | afp-1742, afp-1743, afp-1744, afp-1745 |
The operating voltage range is 11 Vdc to 32 Vdc.
Compatible bases are 5B and MUB (M614).
Yes, they may be intermixed with Minerva and Tyco 614 detectors.