User manual for Tyco FP1600 fire alarm system with features, specs, and programming instructions.
The FP1600 is a microprocessor-based fire alarm system designed for reliable monitoring of up to 16 zones, expandable to 96. It features low power consumption, internal battery and charger, and field programmability with ten detection circuit types. The system supports residential circuits, sprinkler flow switches, and evacuation inputs. It includes a diagnostic display, automated self-test, and history log for efficient maintenance. The unit is available in front or rear service configurations and complies with NZS 4512:2003.
Installation and operation are simplified with removable index panels, 4-wire remote displays, and pushbutton circuit isolation. Ancillary outputs can be programmed for building services control, and the system supports optional brigade interfaces and mimic diagrams. The unit is housed in a compact cabinet with baked epoxy powdercoat finish and is designed for easy servicing and testing.
| Mechanical Dimensions | 510 x 485 x 110 (HWD) per 16 zones |
|---|---|
| Cabinet Material | 1.2 mm mild steel |
| Operating Temperature | 0°C to 45°C |
| Storage Temperature | -20°C to 70°C (without battery) |
| Mains Input | 230 Vac ±10%, 50 Hz, 48W |
| Internal Battery Space | One or two 12V 6.5 Ah sealed lead-acid (not supplied) |
| Internal Charger | 13.65 V (nominal), 2A regulated, temperature compensated |
| Detector Circuits | 96 detector circuits max. (in multiples of 16) |
| Outputs | Evacuation Supervised, up to 3 branches; 12 volts, 3.5 Amps |
| Remote Display | Serial output up to 8 remote displays (3 or 4 wires) |
Up to 16 zones, expandable to 96.
0°C to 45°C.
Yes, using a PC or built-in pushbutton switches and 7-segment displays.
Complies with NZS 4512:2003 and meets New Zealand Fire Service requirements for remote receiving stations.