Pocket quick reference guide for Toshiba RBC-AMT32E and RBC-AMS41E remote controllers, covering fault code display, system data retrieval and configurable…
This pocket quick reference guide from Cool Designs Ltd is written for service engineers working on Toshiba air conditioning equipment. It explains how to use the RBC-AMT32E and RBC-AMS41E remote controllers to display current fault codes and fault code history, and to retrieve system data from connected equipment.
The guide lists indoor and outdoor data codes for Digital/Super Digital Inverter and VRF equipment, describes common configurable control options, and gives simplified instructions for setting time, day and scheduled ON/OFF times on the RBC-AMS41E.
| Supported controllers | RBC-AMT32E and RBC-AMS41E |
|---|---|
| Fault code history capacity | Four fault codes per unit controlled |
| Data access method | Press Test and CL together and hold for 4 seconds |
| Data availability | 0, 1, 2, 3 & 4 Series Digital/Super Digital Inverter and VRF equipment (SMMS, SHRM, SMMSI & SHRMi) |
Press the two yellow Test and Set buttons together and hold for 4 seconds. The first displayed fault code is the youngest; use the TEMP buttons to scroll through the codes.
Press Test and CL together and hold for 4 seconds; codes are shown on the right of the display and data on the left.
Each controller holds four fault codes per unit controlled; the first displayed code is the youngest and the fourth is the oldest.
Press and hold SCHEDULE for 4 seconds, press DAY until the correct day is shown, use the TIME up and down keys to set the time, then press SET.