Rosemount 751 Field Signal Indicator Quick Start Guide

Quick start guide for the Rosemount 751 Field Signal Indicator: assembly, series and parallel wiring, and LCD display configuration.


Rosemount 751 Field Signal Indicator Quick Start Guide - cover page
Brand
Rosemount
Category
Other
Document type
Quick Start Guide
Language
English
Pages
24
File format
PDF
File size
2 MB
Published
16 November, 2026
Updated
16 November, 2026
Model
751
MD5 checksum
5CE79B42C4683D0B6859BF7E9BB56DF0

About this manual

This quick start guide (document 00825-0100-4378, Rev CB, September 2020) gives basic guidelines for the Rosemount 751 Field Signal Indicator. The installation section shows the exploded views of the housing and meter, lists the parts, and provides series and parallel wiring diagrams for connecting the indicator with Rosemount transmitters on a 4–20 mA dc loop. The configuration section explains how to remove the cover, position the decimal point, select the meter function, store the information, set the display values for the 4 mA and 20 mA signals, and replace the cover using the two configuration buttons.

The guide does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, or Explosionproof, Flameproof, or intrinsically safe (I.S.) installations; it refers to the Rosemount 751 Reference Manual for more instruction. It also contains safety warnings about explosions and electrical shock, and includes Product Certification, Declaration of Conformity, and China RoHS sections.

What's inside

  • Installation
  • Assembly
  • Wiring diagrams
  • Configuration
  • LCD display configuration
  • Remove the cover
  • Position the decimal point and select the meter function
  • Store the information
  • Set the display equivalent to a 4 mA signal
  • Set the display equivalent to a 20 mA signal

Specifications

Input signal4–20 mA dc
Bar graph20-segment, factory calibrated
LCD display time-outApproximately 16 seconds
4 mA display setting range–999 to 1000
20 mA display setting range–999 to 9999
MountingU-bolt for 2-in. pipe
Optional conduit bushing¾- to ½-in. conduit reducing bushing

Frequently asked questions

How should the Rosemount 751 be wired when the 4–20 mA transmitter has no test terminal?

It is recommended that the indicator be wired in a series configuration when the transmitter does not contain a test terminal.

How do I store the configuration information?

Press both configuration buttons simultaneously for two seconds; the meter displays “- -” for approximately 7.5 seconds while the information is stored.

Can the meter be removed without disrupting the loop?

The indicator is designed so the analog or LCD display meter can be removed from the housing without impacting the 4–20 mA loop. Removal of the entire device from the series configuration will disrupt the loop.

What is not covered in this quick start guide?

It does not cover configuration, diagnostics, maintenance, service, troubleshooting, or Explosionproof, Flameproof, or intrinsically safe installations; refer to the Rosemount 751 Reference Manual.

Download PDF (2 MB)