Quick start guide for the Rosemount 751 Field Signal Indicator: assembly, series and parallel wiring, and LCD display configuration.
This quick start guide (document 00825-0100-4378, Rev CB, September 2020) gives basic guidelines for the Rosemount 751 Field Signal Indicator. The installation section shows the exploded views of the housing and meter, lists the parts, and provides series and parallel wiring diagrams for connecting the indicator with Rosemount transmitters on a 4–20 mA dc loop. The configuration section explains how to remove the cover, position the decimal point, select the meter function, store the information, set the display values for the 4 mA and 20 mA signals, and replace the cover using the two configuration buttons.
The guide does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, or Explosionproof, Flameproof, or intrinsically safe (I.S.) installations; it refers to the Rosemount 751 Reference Manual for more instruction. It also contains safety warnings about explosions and electrical shock, and includes Product Certification, Declaration of Conformity, and China RoHS sections.
| Input signal | 4–20 mA dc |
|---|---|
| Bar graph | 20-segment, factory calibrated |
| LCD display time-out | Approximately 16 seconds |
| 4 mA display setting range | –999 to 1000 |
| 20 mA display setting range | –999 to 9999 |
| Mounting | U-bolt for 2-in. pipe |
| Optional conduit bushing | ¾- to ½-in. conduit reducing bushing |
It is recommended that the indicator be wired in a series configuration when the transmitter does not contain a test terminal.
Press both configuration buttons simultaneously for two seconds; the meter displays “- -” for approximately 7.5 seconds while the information is stored.
The indicator is designed so the analog or LCD display meter can be removed from the housing without impacting the 4–20 mA loop. Removal of the entire device from the series configuration will disrupt the loop.
It does not cover configuration, diagnostics, maintenance, service, troubleshooting, or Explosionproof, Flameproof, or intrinsically safe installations; refer to the Rosemount 751 Reference Manual.