This manual provides basic installation guidelines for the Rosemount 3144P temperature transmitter, including configuration, switch settings, mounting, wiring, and power supply.
The document provides a five-step quick installation procedure for the Rosemount 3144P HART Temperature Transmitter. The steps include configuring the device using a Field Communicator or AMS, setting security and failure mode switches on the electronics module, mounting the unit (either field-mounted or remote), wiring power connections, and performing a loop test.
Communication requires a loop resistance between 250 and 1100 ohms.
The transmitter must not be operated when power is below 12 Vdc at the terminals.
The power terminals are rated to 42.4 V DC.