Quick installation guide for Rosemount 2051 pressure and 2051CF flow transmitters, covering installation, wiring, jumpers, and certification notes.
This quick installation manual covers Rosemount 2051 intelligent and low-power pressure transmitters and Rosemount 2051CF intelligent and low-power flow transmitters. It outlines six installation steps: installing the transmitter, rotating the housing, setting jumpers and switches, wiring and powering up, parameter settings, and range adjustment.
It also includes mounting and bolt guidance, flange O-ring precautions, 2051T orientation, wiring limits, and certification combination notes, along with safety warnings for explosive atmospheres, process leaks, and electric shock. This manual is written in Chinese.
| Conduit entry thread | 1/2-14 NPT (unless marked) |
|---|---|
| Cable | Twisted pair, 24 AWG or larger, maximum 5000 ft (1500 m) |
| Mounting bracket bolt torque | 125 in.-lbs. (0.9 N·m) |
| Flange bolt torque, carbon steel | Initial 300 in.-lbs.; final 650 in.-lbs. |
| Flange bolt torque, stainless steel | Initial 150 in.-lbs.; final 300 in.-lbs. |
| Housing rotation | Up to 360° |
| Default settings | Alarm high; security off |
If the alarm and security jumpers are not installed, the transmitter defaults to alarm high and security off.
Use twisted pair, 24 AWG or larger, and do not exceed 5000 ft (1500 m).
No; connecting powered test leads can damage the test diode in the test circuit.
The housing can be rotated up to 360 degrees.